S280-75-2
19
Figure 28.
Form 3 tie board test points for internal minimum-trip signal (Table 4). For relationship of terminal location on the tie board, see
Figures 18 and 19.
Figure 27.
Form 3A tie board test points for internal dc-load-current signal
(Table 3). For relationship of terminal location on the tie board, see
figures 20 and 21.
88948KMA
TABLE 4
Tie Board Test Points for Minimum-Trip Signal
Figures 28, 29, and 30)
INTERNAL MINIMUM TRIP SIGNAL
To check the minimum-trip signal, measure the voltage at tie
board test points listed in Table 4.
Failures to get these signals are most likely due to troubles on
the phase-trip No. 2 or ground-trip No. 2 circuit boards or possi-
bly with the phase-trip No.1 or ground-trip No.1 boards. Battery
voltage below 21-Vdc will cause control misoperation of the min-
imum-trip, timing and trip signals of the control. Battery voltage
above 23 volts will operate the circuits correctly. Refer to
“Battery Maintenance,” page 35, for battery charging and testing
information.
Minimum
Terminal Position Voltage Reading Vdc
Trip
Form 3 Form 3A
120%
Signal
Minimum-
+Lead -Lead +Lead -Lead No Fault Trip*
Ph Seq. Ph Seq.
Phase
Min. Relay Min. Relay 25 or
0.30 Max.
Trip 7A
Trip 7A
Battery
Gnd. Seq. Gnd. Seq.
Ground
Min. Relay Min.
Relay 25 or 0.30 Max.
Trip 7A
Trip 7A
Battery
*Voltage reading will last only for the duration of the clearing time of the control
and recloser/simulator.
Содержание Kyle Type ME Series
Страница 34: ...Figure 51 Form 3A test points for battery charging circuitry Table 12 Type ME Electronic Recloser Control 34...
Страница 43: ...Figure 54 continued Form 2 Connections continued 43 S280 75 2...
Страница 44: ...Figure 55 Form 3 connection diagram below S N 5500 Form 3 Connections 44 Type ME Electronic Recloser Control...
Страница 45: ...Figure 55 continued Form 3 Connections continued 45 S280 75 2...
Страница 46: ...Figure 56 Form 3 connection diagram S N 5500 to 25999 46 Type ME Electronic Recloser Control Form 3 Connections...
Страница 47: ...Figure 56 continued 47 S280 75 2 Form 3 Connections continued...
Страница 48: ...Figure 57 Form 3A connection diagram 48 Type ME Electronic Recloser Control Form 3A Connections...
Страница 49: ...Figure 57 continued Form 3A Connections continued S280 75 2 49...