S280-75-2
15
Figure 20.
Form 3A electronic control tie board. The test points listed above will be covered in detail in the "Detailed Circuit Check" section of
this manual.
88948KMA
If a circuit board failure is suspected, always check or
change the diode board first because:
•
The diode board circuits operate in conjunction with the tim-
ing plugs, the output circuit, reset circuit, and reclosing cir-
cuit.
•
A primary diode failure on the diode board can cause sec-
ondary failures on the output board or reclose set board.
NOTE Diode board short circuits are very rare in controls manufactured
after 1970.
If this does not isolate the problem, continue with the circuit
test.