Save Report
Saves the data collected by the Monitor as a report. Up to 8 reports
may be saved from multiple segments and/or multiple locations on
one segment.
Transfer Report
Connect the Monitor to a PC USB port and transfer the saved reports
to Excel files on the PC.
Set Report Names
Customize the names of the reports saved in the Monitor to easily
identify the report source.
Set OK/BAD Limits
Change the limits at which Monitor measurements transition from OK
to BAD to establish customized plant standards.
SPECIFICATIONS
Input voltage
Fieldbus Mode: 8 to 32 VDC
USB Mode: 4.1 to 5.5 VDC
Input current
Fieldbus mode: 10mA max.‡
USB mode: 30mA max.
Power dissipation
Fieldbus mode: 320mW max. (@ 32 VDC)
USB mode: 165mW max. (@ 5.5 VDC)
Operating Temperature
–20 to +50°C *
Dimensions
146 x 88 x 28 mm (5.7 x 3.5 x 1.1 inches)
Weight
378g (0.83lb)
Case Material
ABS
DC Voltage measurement range
8 to 32 ± 0.5 VDC
Signal level measurement range
0.12 to 2 Vpp ±10% ± 25mVpp
Noise measurement ranges
LF (50Hz to 4kHz): 0 to 1000 mVpp ±15% ± 25 mVpp
FF (9kHz to 40kHz): 0 to 1000 mVpp ±10% ± 25 mVpp †
HF (90kHz to 350kHz): 0 to 250 mVpp ±20% ± 25mVpp
Software utility and drivers
Operating system: Windows® XP, Windows® 2000
USB version:
1.1, 2.0
(Note: Vpp = Volts peak-to-peak)
‡ In fieldbus mode the FBT-6-PA is powered by the fieldbus and
draws approximately 9.4mA of current from the segment (depending
on bus voltage and ambient temperature).
* Display update speed is impaired below –10°C
† Excessive noise adjacent to the fieldbus frequency (FF) band will
prevent the FBT-6-PA from reading the fieldbus data and thus reduce
functionality.
Specifications subject to change without notice.
EPS FBT-6-PA-1
Oct 2007