Save Report  

Saves the data collected by the Monitor as a report. Up to 8 reports 
may be saved from multiple segments and/or multiple locations on 
one segment.

Transfer Report  

Connect the Monitor to a PC USB port and transfer the saved reports 
to Excel files on the PC.

Set Report Names  

Customize the names of the reports saved in the Monitor to easily 
identify the report source.

Set OK/BAD Limits  

Change the limits at which Monitor measurements transition from OK 
to BAD to establish customized plant standards.

SPECIFICATIONS

Input voltage

Fieldbus Mode:  8 to 32 VDC
USB Mode:  4.1 to 5.5 VDC

Input current

Fieldbus mode:  10mA max.‡
USB mode:  30mA max.

Power dissipation

Fieldbus mode: 320mW max. (@ 32 VDC)
USB mode: 165mW max. (@ 5.5 VDC)

Operating Temperature

–20 to +50°C *

Dimensions

146 x 88 x 28 mm (5.7 x 3.5 x 1.1 inches)

Weight

378g (0.83lb)

Case Material

ABS

DC Voltage measurement range

8 to 32 ± 0.5 VDC

Signal level measurement range

0.12 to 2 Vpp ±10% ± 25mVpp 

Noise measurement ranges

LF (50Hz to 4kHz): 0 to 1000 mVpp ±15% ± 25 mVpp
FF (9kHz to 40kHz): 0 to 1000 mVpp ±10% ± 25 mVpp †
HF (90kHz to 350kHz): 0 to 250 mVpp ±20% ± 25mVpp

Software utility and drivers

Operating system: Windows® XP, Windows® 2000

USB version: 

1.1, 2.0

(Note: Vpp = Volts peak-to-peak)

‡  In fieldbus mode the FBT-6-PA is powered by the fieldbus and 
draws approximately 9.4mA of current from the segment (depending 
on bus voltage and ambient temperature).

*  Display update speed is impaired below –10°C

†  Excessive noise adjacent to the fieldbus frequency (FF) band will 
prevent the FBT-6-PA from reading the fieldbus data and thus reduce 
functionality.

Specifications subject to change without notice.

EPS FBT-6-PA-1

Oct 2007

Содержание FBT-3

Страница 1: ...Fieldbus Networks Test Equipment FBT 3 FBT 4 FBT 5 FBT 6 FBT 6 PA...

Страница 2: ...network segment by providing measurements of bus power level minimum signal level and peak and average noise level It also displays the number of devices present on the segment and indicates when dev...

Страница 3: ...of the Probe Node frame The signal level is in millivolts Device If there are fieldbus devices active on the network the Monitor counts them If the count has remained the same since the Device functi...

Страница 4: ...dition Following are descriptions of the three indicators Signal indicates that there is bus activity It will only light if data traffic is detected with peak to peak amplitude greater than 150 mV The...

Страница 5: ...the gas clearance must cover the whole system Operation The Wiring Validator has a push button Power switch to turn it on or off If the Wiring Validator is turned on with a single click of the Power...

Страница 6: ...the Wiring Validator is first attached to a wire pair A continuously lit Low Battery light indicates that the batteries need to be replaced Self Test To verify that the Wiring Validator and the Fieldb...

Страница 7: ...number of devices present on the segment and indicates when devices are added or removed from the network It also detects the presence of a short between either of the signal wires and the cable shie...

Страница 8: ...mal and hexadecimal is also displayed This will be the lowest signal level reading from a device since the Monitor was connected to the fieldbus Measurements greater than 150mV are OK Device The addre...

Страница 9: ...easurement range 8 to 32 0 5 V DC Noise measurement ranges LF 50Hz to 4kHz 0 to 1000 mVpp 15 25mVpp FF 9kHz to 40kHz 0 to 1000 mVpp 10 25mVpp HF 90kHz to 350kHz 0 to 250 mVpp 20 25mVpp Signal level me...

Страница 10: ...Class I Zone 2 IIC T4 Ui V Imax Gps A B IIC mA Imax Gps C D IIC IIA mA NIFW 32 1500 1500 FNICO 17 5 274 570 Canada FM C22 2 No 213 C22 2 No 157 CAN CSA E79 0 95 CAN CSA E79 11 95 3028840 Class I Div 1...

Страница 11: ...ther of the signal wires and the cable shield Modern fieldbus commissioning procedures require various bus parameters to be measured and recorded Key parameters include bus voltage signal level for ea...

Страница 12: ...ifficulties may show up on the FBT 6 PA as repeatedly being added or dropped If a device leaves the segment the display shows if a new device is added it shows Device The address in decimal and hexade...

Страница 13: ...0mA max USB mode 30mA max Power dissipation Fieldbus mode 320mW max 32 VDC USB mode 165mW max 5 5 VDC Operating Temperature 20 to 50 C Dimensions 146 x 88 x 28 mm 5 7 x 3 5 x 1 1 inches Weight 378g 0...

Страница 14: ...D IIC IIA mA NIFW 32 1500 1500 FNICO 17 5 274 570 Canada FM C22 2 No 213 C22 2 No 157 CAN CSA E79 0 95 CAN CSA E79 11 95 3028840 Class I Div 1 ABCD T4 Class I Zone 0 and 1 AEx Ex ia IIC T4 Ui V Imax G...

Отзывы: