Profibus-PA 

diagnostic monitor

FBT-6-PA

fieldbus powered

device add & drop indication

shield short indication

measures low, fieldbus and 
high frequency average and 
peak noise 




The Profibus PA Diagnostic Monitor, FBT-6-PA

is used to examine the operation of a live Profibus-PA 
segment without interfering with its operation. The 
Monitor is intended for maintenance personnel to 
verify segment operation or to troubleshoot an errant 
segment.

The FBT-6-PA Diagnostic Monitor

 checks for 

retransmissions from each device on the segment, 
providing a key performance indicator of segment 
health. The Monitor also provides measurements of 
bus voltage level, device signal level, and peak and 
average noise level. It displays the number of devices 
present on the segment and indicates when devices 
are added or removed from the segment. It also 
detects the presence of a short between either of the 
signal wires and the cable shield.

Modern fieldbus commissioning procedures

 

require various bus parameters to be measured 
and recorded. Key parameters include bus voltage, 
signal level for each device and noise level on 
each segment or at every device on each segment.  

Recording the results allows a baseline of the fieldbus 
physical layer to be established. The Monitor collects 
this data, and saves up to eight segment reports 
to be saved for transfer to a PC via a USB port. 
The reports are saved as Microsoft® Excel files as 
a comprehensive commissioning and operations 
report. Considerable savings can be achieved by 
reducing commissioning time and verifying the 
correct operation of the segment.

Data collected from periodic segment

 

verification testing or during troubleshooting can be 
simply transferred to a file for easy comparison to the 
segment baseline/history measurements. Data can 
be displayed as tables and graphs using Microsoft® 
Excel.

Hand-held for portability

, the Monitor is 

powered by the fieldbus so that no battery or 
external power source is required. It includes colour- 
coded test leads and an LCD display.

measures signal level for all    
segment devices

assesses network health

upload measurement data to a 
PC via USB port


EPS FBT-6-PA-1

Oct 2007

Содержание FBT-3

Страница 1: ...Fieldbus Networks Test Equipment FBT 3 FBT 4 FBT 5 FBT 6 FBT 6 PA...

Страница 2: ...network segment by providing measurements of bus power level minimum signal level and peak and average noise level It also displays the number of devices present on the segment and indicates when dev...

Страница 3: ...of the Probe Node frame The signal level is in millivolts Device If there are fieldbus devices active on the network the Monitor counts them If the count has remained the same since the Device functi...

Страница 4: ...dition Following are descriptions of the three indicators Signal indicates that there is bus activity It will only light if data traffic is detected with peak to peak amplitude greater than 150 mV The...

Страница 5: ...the gas clearance must cover the whole system Operation The Wiring Validator has a push button Power switch to turn it on or off If the Wiring Validator is turned on with a single click of the Power...

Страница 6: ...the Wiring Validator is first attached to a wire pair A continuously lit Low Battery light indicates that the batteries need to be replaced Self Test To verify that the Wiring Validator and the Fieldb...

Страница 7: ...number of devices present on the segment and indicates when devices are added or removed from the network It also detects the presence of a short between either of the signal wires and the cable shie...

Страница 8: ...mal and hexadecimal is also displayed This will be the lowest signal level reading from a device since the Monitor was connected to the fieldbus Measurements greater than 150mV are OK Device The addre...

Страница 9: ...easurement range 8 to 32 0 5 V DC Noise measurement ranges LF 50Hz to 4kHz 0 to 1000 mVpp 15 25mVpp FF 9kHz to 40kHz 0 to 1000 mVpp 10 25mVpp HF 90kHz to 350kHz 0 to 250 mVpp 20 25mVpp Signal level me...

Страница 10: ...Class I Zone 2 IIC T4 Ui V Imax Gps A B IIC mA Imax Gps C D IIC IIA mA NIFW 32 1500 1500 FNICO 17 5 274 570 Canada FM C22 2 No 213 C22 2 No 157 CAN CSA E79 0 95 CAN CSA E79 11 95 3028840 Class I Div 1...

Страница 11: ...ther of the signal wires and the cable shield Modern fieldbus commissioning procedures require various bus parameters to be measured and recorded Key parameters include bus voltage signal level for ea...

Страница 12: ...ifficulties may show up on the FBT 6 PA as repeatedly being added or dropped If a device leaves the segment the display shows if a new device is added it shows Device The address in decimal and hexade...

Страница 13: ...0mA max USB mode 30mA max Power dissipation Fieldbus mode 320mW max 32 VDC USB mode 165mW max 5 5 VDC Operating Temperature 20 to 50 C Dimensions 146 x 88 x 28 mm 5 7 x 3 5 x 1 1 inches Weight 378g 0...

Страница 14: ...D IIC IIA mA NIFW 32 1500 1500 FNICO 17 5 274 570 Canada FM C22 2 No 213 C22 2 No 157 CAN CSA E79 0 95 CAN CSA E79 11 95 3028840 Class I Div 1 ABCD T4 Class I Zone 0 and 1 AEx Ex ia IIC T4 Ui V Imax G...

Отзывы: