ControlKeeper

®

 4

InstallatIon sheet

Model# CK4-120no

-

Model# CK4-277no

General Information

The ControlKeeper-4 model is shipped in one package and 

is configured with either a 120V or a 277V transformer. It is 

factory configured with Normally Open relays. Please refer 

to your order information to determine which model you have 

purchased. 

Getting Started

1.  Do not discard these installation instructions. Please keep 

for future reference and operation information.

2.  Always disconnect all power before wiring.

3.  Use only as intended and at the listed voltage.

4.  All installation and service must be performed by qualified 

personnel or service technicians.

5.  Install in accordance with the National Electrical Code and 

any other codes which may apply.

6.  Installation and wiring information contained in this docu

-

ment is based on industry-accepted standards and prac

-

tices. If conflicts exist between these instructions and any 

applicable codes or ordinances, please contact Greengate 

before proceeding with the installation.

7.  High Voltage is present inside the enclosure. Use extreme 

caution when performing maintenance on this equipment.  

Failure to follow this warning and proper safety procedures 

could result in severe injury or death, and/or damage to 

the equipment.

8.  Document all wiring and device terminations and loca

-

tions  so  that  devices  can  be  properly  configured  and 

programmed for operation.

Mounting the Cabinet

1.  Choose a dry location on a firm surface convenient to the 

circuits being controlled.  Allow full clearance for the door 

of the enclosure to open fully.

2.  Mount the ControlKeeper-4 cabinet using the holes pro

-

vided in the back of the enclosure. It is recommended that 

the panel be mounted vertically.

3.  All Line Voltage conductors must enter the cabinet on the 

right side of the enclosure.

4.  All Low Voltage conductors must enter the cabinet on the 

left side of the enclosure.

5.  Remove all debris and metal shavings from the enclosure 

before applying power to the ControlKeeper-4.

Figure-1 ControlKeeper-4 Enclosure

Power Supply Wiring

The ControlKeeper-4 is factory configured with either a 120V 

or a 277V transformer. Transformer voltages are color coded. 

It is recommended that a dedicated branch circuit with circuit 

protection be used for power supply wiring.
1. Connect neutral wire to the white wire.
2. If the transformer is a 277V model, connect orange wire to  

    a 277V circuit. If the transformer is a 120V model, connect  

    black wire to a 120V circuit.

Figure-1 ControlKeeper-4 Enclosure

Connecting Relay Loads

1. Test branch circuits for short circuits prior to connecting and
    energizing the ControlKeeper-4.
2. Relay terminal blocks have a maximum limit of 10 AWG wire.
3. Relays are rated for single-pole circuit use. Connection of 2
    pole circuits/loads to the ControlKeeper-4 will void the   

    equipment warranty.
4. Connect a 120 or 277 volt, 20 amp maximum, de-en- 

 

   ergized  branch  circuit  breaker  to  the  relay  terminal  block 

 

    position labeled LINE.

Line = 120V (Black),

277V (Orange)

Neutral = White

277V Transformer

Line = Orange

Neutral = White

120V Transformer

Line = Black

Neutral = White

Cooper Controls

203 Cooper Circle, Peachtree, Ga 30269

800-553-3879

www.coopercontrol.com 

Содержание Greengate CK4-120NO

Страница 1: ...s being controlled Allow full clearance for the door of the enclosure to open fully 2 Mount the ControlKeeper 4 cabinet using the holes pro vided in the back of the enclosure It is recommended that the panel be mounted vertically 3 All Line Voltage conductors must enter the cabinet on the right side of the enclosure 4 All Low Voltage conductors must enter the cabinet on the left side of the enclos...

Страница 2: ... ControlKeeper 4 panel 5 If using Belden 9841 or 89841 leave all shields disconnected making certain that shield is not exposed 6 Panels and devices on the RS 485 lighting network should be daisy chained Do not create a Star or T Tapped configuration 7 Total network length should not exceed 4000 feet Network Wiring Details 1 Before wiring select the two panels that are going to be the end panels o...

Страница 3: ...voltage wiring is Class 2 wiring 2 All low voltage wiring must enter the cabinet into the Low Voltage section of the enclosure Low Voltage wiring can be brought into the enclosure from the left side of the enclosure Failure to separate high voltage from low voltage wiring may cause interference with logic board function 3 All low voltage wiring must be run in separate conduit from line voltage wir...

Страница 4: ...a daisy chain con figuration No T Taps Stars should be used The GDS I device should reside somewhere within the daisy chain switch net work Total daisy chain network length should not exceed 1000 feet The following instructions describe the GDS I device connec tion to the ControlKeeper 4 Please refer to the Digital Switch Installation Instructions for information on wiring the Digital Switch netwo...

Страница 5: ... for relays to run programmed scheduling the hardware override switch must be in the AUTO or center position See Figure 9 for location of the hardware override switch LED Operation The ControlKeeper 4 has LEDs for status monitoring They consist of System Status LEDs and Relay Status LEDs Figure 10 ControlKeeper 4 Status LEDs System Status LEDs There are six 6 system status LEDs that are located in...

Страница 6: ...ft Reset Command press in and then immediately release the reset button in the lower right corner of the logic panel When the reset button is pressed and released the status LED may hesitate briefly then resume normal operation Clear Settings Command A clear settings command is used to remove all programming from a ControlKeeper 4 unit It should be done before downloading programming to the unit f...

Страница 7: ...et Switch 8 Network Terminator Jumper 9 Network Wiring Terminal Block 10 Digital Switch Port 11 Panel Communications Port 12 Peripheral Power Terminal 24VDC DC Ground 13 Switch Input Wiring Channels 14 Panel Network Address DIP Switches Item Reference The ControlKeeper 4 consists of a logic board with a clear separation of line voltage and low voltage components There are several features of note ...

Страница 8: ...modification or misapplication by damage during shipment or by improper service There are no warranties which extend beyond the hereinabove limited warranty INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS No employee agent dealer or other person is authorized to give any warranties on behalf of the Seller or to assume for the Seller any othe...

Отзывы: