                            Figure-4 Network Wiring Detail
                Figure-5 Item Reference for Network Details

All panels must be assigned a unique Network Address in order to
communicate over the lighting network. Switch positions are
labeled 1 through 8 and are valued at 1 through 128 as shown above.
The network address is calculated by adding the value of the switch
positions that are in the ON position. In the example above,
switches 1 and 3 are ON giving the panel the network address of 5.
Addresses 1 through 254 are valid addresses. Zero and 255 are
reserved for system use. To initialize the network address with the
controller, press the panel reset button after the address is set.

 

 

         Figure-6 Address Switch Information

Connecting Low Voltage Inputs

The ControlKeeper-4 logic board can support both dry contact
closure and Digital Switch inputs. If a combination of contact
input switches and Digital Switches are being used, the com-
bined total cannot exceed 64 inputs.
Regardless of input type used, it is recommended that all input
wiring be done prior to applying power to the logic board or at
the very least with the terminal blocks removed from the logic
board. Please verify that there are no shorts to AC Ground
prior to connection of input devices. Regardless of input type,
the following notes apply.
1. All low voltage wiring is Class 2 wiring.
2. All low voltage wiring must enter the cabinet into the Low
    Voltage section of the enclosure. Low Voltage wiring can be
     brought into the enclosure from the left side of the enclosure.
    Failure to separate high voltage from low voltage wiring
    may cause interference with logic board function.
3. All low voltage wiring must be run in separate conduit from
    line voltage wiring.
4. Test all low voltage wiring for shorts to AC ground before
    connection to the relay panel.
5. When powering peripheral devices such as motion sensors
           and photosensors from the ControlKeeper-4 panel, there
    may be a limitation on the number of sensors that can be
     supported. This is also true if Digital Switches are used with
   the system. See the recommendations below or contact
    Cooper Controls for further information.
6. It is recommended that the terminal blocks be removed from
    the board or power removed from the logic board when
    doing initial switch input wiring.

Contact Input Switch Wiring

This section describes the wiring for dry contact closure de

-

vices. There are four switch input wiring terminals on the left 

side of the ControlKeeper-4 to allow for wiring of the dry contact 

closure devices.
1. Use 18 AWG twisted, unshielded wire for all low voltage dry
    contact closure device wiring.
2. Maximum length for dry contact closure device wiring is
    1000 feet.
3. Please see wiring detail below for details on connections
    of different devices to the ControlKeeper-4 system.

MOV1

MOV3

MOV2

MOV4

TB1

TB2

TB3

TB4

Relay Rating: 20amps, 208/240/480V

Wire: 6 AWG Max.

Relay Wiring

Q2

Q1

P1

LED9

K1

K2

LED1

LED5

U3

U2

U1

SW1

SW3

U4

PCI 2004

C

X4 

TPR

C

ST

ATUS

50-022140-00

LINE

LO

AD

LINE

LO

AD

To Lighting Load

To Circuit Breaker #1

To Circuit Breaker #2

To Lighting Load

Page 3

Содержание Greengate CK4-120NO

Страница 1: ...s being controlled Allow full clearance for the door of the enclosure to open fully 2 Mount the ControlKeeper 4 cabinet using the holes pro vided in the back of the enclosure It is recommended that the panel be mounted vertically 3 All Line Voltage conductors must enter the cabinet on the right side of the enclosure 4 All Low Voltage conductors must enter the cabinet on the left side of the enclos...

Страница 2: ... ControlKeeper 4 panel 5 If using Belden 9841 or 89841 leave all shields disconnected making certain that shield is not exposed 6 Panels and devices on the RS 485 lighting network should be daisy chained Do not create a Star or T Tapped configuration 7 Total network length should not exceed 4000 feet Network Wiring Details 1 Before wiring select the two panels that are going to be the end panels o...

Страница 3: ...voltage wiring is Class 2 wiring 2 All low voltage wiring must enter the cabinet into the Low Voltage section of the enclosure Low Voltage wiring can be brought into the enclosure from the left side of the enclosure Failure to separate high voltage from low voltage wiring may cause interference with logic board function 3 All low voltage wiring must be run in separate conduit from line voltage wir...

Страница 4: ...a daisy chain con figuration No T Taps Stars should be used The GDS I device should reside somewhere within the daisy chain switch net work Total daisy chain network length should not exceed 1000 feet The following instructions describe the GDS I device connec tion to the ControlKeeper 4 Please refer to the Digital Switch Installation Instructions for information on wiring the Digital Switch netwo...

Страница 5: ... for relays to run programmed scheduling the hardware override switch must be in the AUTO or center position See Figure 9 for location of the hardware override switch LED Operation The ControlKeeper 4 has LEDs for status monitoring They consist of System Status LEDs and Relay Status LEDs Figure 10 ControlKeeper 4 Status LEDs System Status LEDs There are six 6 system status LEDs that are located in...

Страница 6: ...ft Reset Command press in and then immediately release the reset button in the lower right corner of the logic panel When the reset button is pressed and released the status LED may hesitate briefly then resume normal operation Clear Settings Command A clear settings command is used to remove all programming from a ControlKeeper 4 unit It should be done before downloading programming to the unit f...

Страница 7: ...et Switch 8 Network Terminator Jumper 9 Network Wiring Terminal Block 10 Digital Switch Port 11 Panel Communications Port 12 Peripheral Power Terminal 24VDC DC Ground 13 Switch Input Wiring Channels 14 Panel Network Address DIP Switches Item Reference The ControlKeeper 4 consists of a logic board with a clear separation of line voltage and low voltage components There are several features of note ...

Страница 8: ...modification or misapplication by damage during shipment or by improper service There are no warranties which extend beyond the hereinabove limited warranty INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS No employee agent dealer or other person is authorized to give any warranties on behalf of the Seller or to assume for the Seller any othe...

Отзывы: