Page 8
Specifications
5
Outdoor Unit
Specifications
Indoor units that can be used in
combination
Number of connected
units
1-5 units
Compressor stop/start frequency
Stop time
3 minutes or more
Voltage fluctuation
within ± 10% of rated voltage
Power source voltage
Voltage drop during start
within ± 15% of rated voltage
Interval unbalance
within ± 3% of rated voltage
1 drive 2 1 drive 3
Max. length for all rooms
98.4/30
147.6/45
Max. length for one indoor unit
65.6/20
82/25
Max. height different between
indoor and outdoor unit
OU higher than IU
32.8/10
32.8/10
OU lower than IU
49/15
49/15
Max. height difference between indoor units
32.8/10
32.8/10
1 drive 4
1 drive 5
196.8/60
246/75
98.4/30
98.4/30
32.8/10
32.8/10
49/15
49/15
32.8/10
32.8/10
Unit: ft/m
49ft (15m)
When installing multiple indoor units to a single outdoor unit, ensure that the length of the refrigerant
pipe and the drop height between the indoor and outdoor units meet the following requirements:
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
49ft (15m)
32.8ft (10m)
Max. height difference