 Page 12 

Refrigerant Piping Connection

7

Safety Precautions

 

WARNING

  All field piping must be completed by a 

licensed technician and must comply with

local and national regulations. 

  When the air conditioner is installed in a small 

room, measures must be taken to prevent the 

refrigerant concentration in the room from 

exceeding the safety limit in the event of 

refrigerant leakage. If the refrigerant leaks 

and its concentration exceeds its proper limit, 

hazards due to lack of oxygen may result.     

   When installing the refrigeration system, 

ensure that air, dust, moisture, or foreign 

substances do not enter the refrigerant circuit. 

Contamination in the system may cause poor 

operating capacity, high pressure in the 

refrigeration cycle, explosion, or injury.     

  Ventilate the area immediately if there is 

refrigerant leakage during the installation. 

Leaked refrigerant gas is both toxic and 

flammable. Ensure there is no refrigerant 

leakage after completing the installation work.    

Refrigerant Piping 

Connection

Refrigerant Piping Connection Instructions

 CAUTION

• 

The branching pipe must be installed 

horizontally. An angle of more than 10° may 

cause malfunction. 

• 

DO NOT 

install the connecting pipe until both 

the indoor unit and the outdoor unit have 

been installed.

 

• 

Insulate the gas and liquid piping to 

prevent water leakage. 

Step1: Cut pipes

When preparing refrigerant pipes, take extra 

care to cut and flare them properly. This will 

ensure efficient operation and minimize the 

need for future maintenance.   
1. Measure the distance between the indoor 

and outdoor units. 

2. Using a pipe cutter, cut the pipe a little 

longer than the measured distance. 

 CAUTION

DO NOT 

deform pipe while cutting. Be extra 

careful not to damage, dent, or deform the pipe 

while cutting. This will drastically reduce the 

heating efficiency of the unit.  

 

1. Make sure the pipe is cut at a perfect 

90° angle. Refer to Fig. 7.1 for examples of 

bad cuts. 

Oblique

Rough

Warped

90°

Fig. 7.1

Step 2: Remove burrs

Burrs can affect the air-tight seal of the refrigerant

piping connection. They must be completely 

removed. 

1. Hold the pipe at a downward angle to 

prevent burrs from falling into the pipe. 

2. Using a reamer or deburring tool, remove 

all burrs from the cut section of the pipe. 

Pipe

Reamer

Point down

Fig. 7.2

Step 3: Flare pipe ends

Proper flaring is essential to achieve an airtight seal.

1. After removing burrs from the cut pipe, seal 

the ends with PVC tape to prevent foreign 

materials from entering the pipe. 

2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of the pipe. 

Make sure they are facing in the right 

direction because you can’t put them on 

or change their direction after flaring

(see Fig. 7.3).

Flare nut

Copper pipe

Fig. 7.3

Содержание SOPHIA CH-18MSPH-230VO

Страница 1: ...fore installing or operating your new air conditioning unit Make sure to save this manual for future reference This manual only describes the installation of the outdoor unit When installing the indoo...

Страница 2: ...stallation Instructions 09 B Drain Joint Installation 11 C Notes on Drilling the Hole in the Wall 11 D When Selecting a 24K Indoor Unit 11 Table of Contents Installation Manual Installation Diagram 07...

Страница 3: ...nnection 12 Wiring 14 A Outdoor Unit Wiring 14 B Wiring Figure 16 Air Evacuation 20 A Evacuation Instructions 20 B Note on Adding Refrigerant 21 22 23 Test Run Function of Automatic Wiring Piping Corr...

Страница 4: ...r connector packed with the indoor unit or outdoor unit depending on the model NOTE Pipe sizes differ from appliance to appliance To meet different pipe size requirements sometimes a transfer connecto...

Страница 5: ...your unit and locate it accordingly Failure to do so could cause damage to the unit After installation ensure there are no refrigerant leaks and that the unit is operating properly Refrigerant is toxi...

Страница 6: ...Unit Installation Overview L N 1 2 3 MC MC 4 5 INSTALLATION ORDER Install the outdoor unit Page 9 Evacuate the refrigeration system Page 20 Connect the wires Page 14 Connect the refrigerant pipes Pag...

Страница 7: ...nt unnecessary damage to the wall use a stud finder to locate studs A minimum pipe run of 9 8 ft 3 m is required to minimize vibration and excessive noise Two of the A B and C directions should be fre...

Страница 8: ...47 6 45 Max length for one indoor unit 65 6 20 82 25 Max height different between indoor and outdoor unit OU higher than IU 32 8 10 32 8 10 OU lower than IU 49 15 49 15 Max height difference between i...

Страница 9: ...tween the outdoor and indoor units must not exceed the maximum allowable pipe length If possible DO NOT install the unit where it will be exposed to direct sunlight If possible make sure the unit is l...

Страница 10: ...12 6 22 560 13 2 335 900 x 860 x 315 35 4 x 33 85 x 12 4 23 2 590 13 1 333 945 x 810 x 395 37 2 x 31 9 x 15 55 25 2 640 15 95 405 990 x 965 x 345 38 98 x 38 x 13 58 24 58 624 14 4 366 946 x 810 x 420...

Страница 11: ...al on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain joint into the hole in the base pan of the unit 3 Rotate the drain joint 90 until it clicks in place facing th...

Страница 12: ...nsulate the gas and liquid piping to prevent water leakage Step1 Cut pipes When preparing refrigerant pipes take extra care to cut and flare them properly This will ensure efficient operation and mini...

Страница 13: ...hten the flare nut as tightly as possible by hand 4 Using a spanner grip the nut on the unit tubing 5 While firmly gripping the nut use a torque wrench to tighten the flare nut according to the torque...

Страница 14: ...of the power cord or use an extension cord CAUTION Connect the outdoor wires before connecting the indoor wires Make sure to ground the unit The grounding wire should be away from gas pipes water pipe...

Страница 15: ...he wiring diagram found inside the electrical box cover 2 Remove the electric cover of the outdoor unit If there is no cover on the outdoor unit disassemble the bolts from the maintenance board and re...

Страница 16: ...minals as identified with their respective matched numbers on the terminal block of the indoor and outdoor units For example see the following US models Terminal L1 A on the outdoor unit must connect...

Страница 17: ...ring NOTE If the client wants to perform the wiring himself refer to the following figures One three models One four models Model A Model B Model C Model D Model A Model B Model C Model D Model E Mode...

Страница 18: ...Page 18 Wiring One five models Model A Model B Model C Model D Model E Model F Model G...

Страница 19: ...oist area from vibrations to which the unit will be subjected during the course of transportation Check to make sure they are all tightly fastened If they are loose the wires could burn out The follow...

Страница 20: ...wise a 1 4 turn Listen for gas to exit the system then close the valve after 5 seconds Flare nut Cap Valve body Valve stem Fig 9 2 9 Watch the Pressure Gauge for one minute to make sure that there is...

Страница 21: ...gth standard pipe length x N x 0 16 oZ ft Liquid Side 9 52 3 8 Total pipe length standard pipe length x N x 30 g m Total pipe length standard pipe length x N x 0 32 oZ ft Electrical safety check Perfo...

Страница 22: ...p valves 2 Turn on the main power switch and allow the unit to warm up 3 Set the air conditioner to COOL mode 4 For the indoor unit A Ensure the remote control and its buttons work properly B Ensure t...

Страница 23: ...te This Function 1 Check that the outside temperature is above 41 F 5 C This fuction does not work when the outside temperature is not above 41 F 5 C 2 Check that the stop valves on the liquid and gas...

Страница 24: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details www cooperandhunter us...

Отзывы: