![Cooper & Hunter CHV-5S224SNMX Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/cooper-and-hunter/chv-5s224snmx/chv-5s224snmx_service-manual_2661802056.webp)
INSTALLATION
0
54
0
CHV
5 COM PACT MULTI VRF UNIT
SERVICE M ANUAL
(3) The insulation thickness of condensate water pipe: at least 10 mm;
(4) When the diameter of copper pipe is equal to or greater than Φ15.9 mm, the thickness of insulation material
should be at least 20mm; when the diameter of copper pipe is less than 15.9 mm, the thickness of insulation
material should be at least 15 mm.
3.4 Communication cable and control cable
Note:
For air conditioning units installed in places with strong electromagnetic interference, shielded wire must be
used as the communication cables of the IDU and wired controller, and shielded twisted pairs must be used as the
communication cables between IDUs and between the IDU and ODU.
①
The communication wire between indoor unit and wire controller
Material
Length L(m)
Sectional area (mm
2
)
standard
Remarks
RVV
L≤250
≥2×0.75
GB/T 5023.3-2008
L≤250m
Note: The following table shows the length (L) of the communication wire between indoor unit and wire
controller.
②
The communication wire between indoor unit and outdoor (or indoor) unit.
Material
Length L(m)
Sectional area
(mm
2
)
standard
Remarks
RVV
L≤1000
≥2×0.75
GB/T 5023.3-2008
If the diameter increases to 2×1mm
2
, the
length (L) should enlarge. But the length
(L) should be less than 1500m.
Note: The following table shows the
length (L) of
the communication wire between indoor unit and outdoor (or
indoor) unit, the
sectional area
of communication wire.L=L1+L2+
﹒ ﹒ ﹒
+Ln.
Содержание CHV-5S224SNMX
Страница 1: ...CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL R410A 50 60Hz...
Страница 3: ...1 PRODUCT CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL PRODUCT...
Страница 11: ...0 900 CONTROL CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL CONTROL...
Страница 50: ...INSTALLATION 0 48 0 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL INSTALLATION...