0
53 INSTALLATION
CHV
5 COM PACT MULTI VRF UNIT
SERVICE M ANUAL
The materials, equipment and instruments used during air conditioning engineering construction must have
certifications and test reports. Products with fireproof requirements must be provided with fireproof inspection
certificates and must meet national and relevant compulsory standards. If environmentally-friendly mater ials are to
be used as required by customers, all such materials must meet national environmental protection requirement and
be provided with relevant certificates.
3.1 Refrigerant piping
(1) Material requirement: Dephosphorization drawing copper pipe for air conditioners;
(2) Appearance requirement: The inner and outer surface of pipe should be smooth without pinhole, crack,
peeling, blister, inclus ion, copper powder, carbon deposition, rust, dirt or severe oxide film, and without obvious
scratch, pit, spot and other defects.
(3) Test report: Certifications and quality test reports must be provided.
(4) The tensile strength must be at least 240 kgf/mm²
.
(5) Specifications requirement
OD
(
mm
)
Refrigerant
Wall Thickness
(
mm
)
Model
6.35
R410A
0.8
0
9.52
R410A
0.8
0
12.7
R410A
0.8
0
15.88
R410A
1.0
0
19.05
R410A
1.0
0
1/2H
22.2
R410A
1.5
1/2H
(6) After the inner part of the copper pipe is cleaned and dried, the inlet and outlet mus t be sealed tightly by
using pipe caps, plugs or adhesive tapes.
3.2 Condensate water pipe
(1) Pipes that can be used for air conditioner drainage include: water supplying UPVC pipe, PP -R pipe, PP-C pipe,
and HDG steel pipe;
(2) All relevant certificates and quality test reports are provided.
(3) Requirements for specifications and wall thickness
Water supplying UPVC pipe:
Φ
32mm
×
2mm
,
Φ40mm
×
2mm
,
Φ50mm×2.5mm;
HDG steel pipe:
Φ
25mm
×
3.25mm
,
Φ32mm×3.25mm
,
Φ40mm×3.5mm
,
Φ50mm×3.5mm.
3.3 Insulation material
(1) Rubber foam insulation material;
(2) Flame retardancy level: B1 or higher; Refractoriness: at least 120oC.
Содержание CHV-5S224SNMX
Страница 1: ...CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL R410A 50 60Hz...
Страница 3: ...1 PRODUCT CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL PRODUCT...
Страница 11: ...0 900 CONTROL CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL CONTROL...
Страница 50: ...INSTALLATION 0 48 0 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL INSTALLATION...
Страница 74: ...MAINTENACE 0720 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL Maintenace...
Страница 120: ...MAINTENACE 01180 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL...