115 MAINTENACE
CHV
5 COM PACT MULTI VRF UNIT
SERVICE M ANUAL
d
c
b
a
室内机
①
②
③
④
B
A
C
室外机
D
Indoor Unit
:
No.
Model
Indoor Unit
①
Cassette type
CHV
-5SC71NK
Indoor Unit
②
Wall-mounted type
CHV
-5SW36NK
Indoor Unit
③
Duct type
CHV
-5SD5
0
NK
Indoor Unit
④
Duct type
CHV
-5SD25NK
Liquid Pipe
:
No.
A
B
C
D
Diameter
of pipe
φ
9.52
φ
9.52
φ
9.52
φ
6.35
Length
20m
10m
5m
5m
No.
a
b
c
d
Diameter
of pipe
φ
9.52
φ
6.35
φ
6.35
φ
6.35
Length
10m
10m
10m
10m
Length of Liquid Pine
:
φ
9.52
:
A+B+C+a=20+10+5+10=45m
φ
6.35
:
D+b+c+d=5+10+10+10=35m
L= (φ9.52Length of liquid pipe)
×
1+(φ6.4 Length of liquid pipe)
×
0.4
= 45
×
1+35
×
0.4=59m
LA=L-50=59-50=9 m
Additional volume of refrigerant R=LA
×
54 =9
×
54=486 g
b. Operation procedure for adding refrigerant
b1. Put the charging tank on the weightometer, record the reading and then calculate the data after charging
refrigerant;
b2. Use charging conduct pipe to connect the double-ended manometer with governing valve and liquid-charging
tank to the detection head of gas valve and liquid valve. Before connection, please release some refrigerant and
then drain out the air inside the charging conduct pipe;
Outdoor unit
Indoor unit
Содержание CHV-5S224SNMX
Страница 1: ...CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL R410A 50 60Hz...
Страница 3: ...1 PRODUCT CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL PRODUCT...
Страница 11: ...0 900 CONTROL CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL CONTROL...
Страница 50: ...INSTALLATION 0 48 0 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL INSTALLATION...
Страница 74: ...MAINTENACE 0720 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL Maintenace...
Страница 120: ...MAINTENACE 01180 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL...