background image

6

WARNING

    

    Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior 
    to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.    
     a) Become familiar with the equipment and its operation.  
     b) Isolate system electrically. 
     c) Before attempting the procedure ensure that:
       • Mechanical  handling  equipment  is  available, if required, for handling refrigerant cylinders; 
       • All personal protective equipment is available and being used correctly; 
       • The recovery process is supervised at all times by a competent person; 
       • Recovery equipment and cylinders conform to the appropriate standards. 
     d) Pump down refrigerant system, if possible. 
     e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the 
         system. 
     f) Make sure that cylinder is situated on the scales before recovery takes place. 
     g) Start the recovery machine and operate in accordance with manufacturer's instructions. 
     h) Do not overfill cylinders. (No more than 80 % volume liquid charge). 
     i) Do not exceed the maximum working pressure of the cylinder, even temporarily. 
     j) When the cylinders have been filled correctly and the process completed, make sure that  the cylinders and 
        the equipment are removed from site promptly and all isolation valves on the equipment are closed off. 
    k) Recovered refrigerant shall not be charged into another refrigeration system unless it has 
        been cleaned and checked.

15. 

Labelling

      Equipment shall be labelled stating that it has been de-commissioned and emptied of  refrigerant.    
      The label shall be dated and signed. 
      Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

16.   

Recovery

      • When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good 
        practice that all refrigerants are removed safely. 
      • When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are 
        employed.
      • Ensure that the correct number of cylinders for holding the total system charge is available.    
      • All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. 
        special cylinders for the recovery of refrigerant). 
      • Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. 
      • Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. 
      • The recovery equipment shall be in good working order with a set of instructions concerning the equipment 
         that is at hand and shall be suitable for the recovery of flammable refrigerants. 
      • In addition, a set of calibrated weighing scales shall be available and in good working order.   
      • Hoses shall be complete with leak-free disconnect couplings and in good condition. 
      • Before using the recovery machine, check that it is in satisfactory working order, has been properly 
        maintained and that any associated electrical components are sealed to prevent ignition in the event of a 
        refrigerant release. 
      • Consult manufacturer if in doubt.
      • The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and 
         the relevant Waste Transfer Note arranged. 
      • Do not mix refrigerants in recovery units and especially not in cylinders. 
      • If compressors or compressor oils are to be removed, ensure that they have been evacuated to an 
        acceptable level to make certain that flammable refrigerant does not remain within the lubricant. 
      • The evacuation process shall be carried out prior to returning the compressor to the suppliers. 
      • Only electric heating to the compressor body shall be employed to accelerate this process.    
      • When oil is drained from a system, it shall be carried out safely.          
                 

DC Inverter E

-

Series 

Duct Type

 Unit 

Содержание CH-ID0100RKE

Страница 1: ...u have lost the Owner s Manual please contact the local agent or visit www cooperandhunter com or sent email to info cooperandhunter com or electronic version C H reserves the right to interpret this...

Страница 2: ...Safety Notice 11 2 The Tools and Instruments for Installation 12 3 The Installation of the Indoor Unit 12 3 1 The Initial Check 12 3 2 Installation 13 4 Refrigerant Pipe 15 4 1 The Pipe Material 15 4...

Страница 3: ...installed must have the reliable electrical grounding facility and protection Please do not connect the grounding of this product to various kinds of air feeding ducts drain piping lightning protecti...

Страница 4: ...ating of circuit breakers ELB is detailed in outdoor instruction manual The method of connection of the appliance to the electrical supply and interconnection of separate components is detailed in bel...

Страница 5: ...vapour being present while the work is being performed 6 3 General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out Wor...

Страница 6: ...ment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak dete...

Страница 7: ...rcuit with inert gas Evacuate Purge again with inert gas Open the circuit by cutting or brazing The refrigerant charge shall be recovered into the correct recovery cylinders The system shall be flushe...

Страница 8: ...cing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinder...

Страница 9: ...uthority which authoriaes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification Servicing shall only be performed as recommended by the equi...

Страница 10: ...ll be further specified in remote controller s manual Please read it carefully before using this appliance and keep it for future reference Remote controller optional ON OFF MODE FAN SLEEP SUPER SMART...

Страница 11: ...essor must run for at least 5 minutes once operational In the 5 minutes compressor will not stop even the room temperature reaches the setting temperature point unless you use remote controller to tur...

Страница 12: ...ng with mode interfere occurs Following shows the mode interfere scene Cooling Dry Heating Fan Cooling normal Dry mode interfere Heating Fan Outdoor unit always run with the mode of first indoor unit...

Страница 13: ...irmly clamp the interconnecting wires so their terminals receive no external stresses Incomplete connections or clamping may cause terminal overheating or fire After connecting all the wires be sure t...

Страница 14: ...it mm unit mm During installation do not damage the insulation material on the surface of the indoor unit Number 1 2 3 4 5 6 7 Tool Standard screwdriver Vacuum pump Charge hose Pipe bender Adjustable...

Страница 15: ...nd noise in electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if a one meter allowance is maintained Do not install the indoor un...

Страница 16: ...from loosening 1 During the installation please cover the unit with the plastic cloth to keep it clean 2 Make sure that the unit is installed level by using a level or a plastic tube filled with water...

Страница 17: ...rs 3 After finishing connecting the refrigerant pipes keep it warm with the insulation material Fig 4 4 Piping insulation procedure 030 071 085 100 125 160 DANGER The pipe go through the hole with the...

Страница 18: ...e causing water leakage Drain piping passing indoors Drain sockets Referring the figure below insulate the drain socket and drain hose using the included large sealing pad Drain piping connections Do...

Страница 19: ...trol box 17 WARNING Fig 6 1 6 Electrical Wiring When clamping the wiring use the included clamping material as shown in the Fig 6 1 to prevent external pressure being exerted on the wiring connections...

Страница 20: ...until display 17 and press ENTER button to entering system parameter adaption state symbol stop blinking Select desired parameter code 10 by pressing button and press ENTER button to confirm Select d...

Страница 21: ...n the table are selected at the maximus current of the unit according to the European Standard En60 335 1 Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord c...

Страница 22: ...nt possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use...

Отзывы: