3
7
9.3.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution
(P0)
Error Code
P0
Malfunction decision
conditions
When the voltage signal that IPM send to compressor drive chip
is abnormal, the display LED will show “P0” and AC will turn off.
Supposed causes
●
Wiring mistake
●
IPM malfunction
●
Outdoor fan ass’y faulty
●
Compressor malfunction
●
Outdoor PCB faulty
Trouble shooting:
For 9K~18K:
Check if the wiring between main
PCB and compressor. If the wires
and connectors are broken?
Correct the connection or replace
the wires and connectors.
Yes
No
IPM continuity check. Check if the
IPM terminal resistance values are
uniform.
Replace the IPM board or replace the
main PCB if the IPM board and main
PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
Please refer to the solution of
【
Fan Speed Has Been
Out Of Control
】
malfunction
Yes
Check if the compressor resistance
values are uniform.
No
Replace the compressor.
Yes
Replace the outdoor main PCB if the
main PCB and IPM are separate.
Содержание CH-09DKT230VI
Страница 29: ...27 IPM board TO MAIN W connecttothecompressor V OVAC standby 10 200VAC running...
Страница 41: ...39 P W N U...
Страница 42: ...40 N V N W...