COOLMAY EX3G PLC/HMI All in one Programming manual
25
(Negative temp)
PT100/PT1000
-200
~
350
℃
-2000
~
3500
0.1
℃
1%
NTC
-48
~
210
℃
-480
~
2100
0.1
℃
1%
Voltage
0
~
10V/0-5V
0
~
4000
2.5mV
1%
Current Type1
0
~
20mA
0
~
4000
5uA
1%
Current Type2
4
~
20mA
0
~
4000
4uA
1%
Below table for software version 26230 and above
Input signal
Range
Register value
Resolution
Accuracy
(Total Measuring
range)
K-type thermocouple
0
~
1100
℃
Room temperature
~
11000
0.1
℃
1%
K-type thermocouple
(Negative temp)
-210
~
1200
℃
-2100
~
12000
0.1
℃
1%
T-type thermocouple
0
~
420
℃
Room temperature
~
4200
0.1
℃
1%
T-type thermocouple
(Negative temp)
-210
~
420
℃
-2100
~
4200
0.1
℃
1%
S-type thermocouple
0
~
1710
℃
Room temperature
~
17100
0.1
℃
1%
S-type thermocouple
(Negative temp)
-26
~
1710
℃
-260
~
17100
0.1
℃
1%
J-type thermocouple
0
~
800
℃
Room temperature
~
8000
0.1
℃
1%
J-type thermocouple
(Negative temp)
-90
~
950
℃
-900
~
9500
0.1
℃
1%
E-type thermocouple
0
~
600
℃
Room temperature
~
6000
0.1
℃
1%
E-type thermocouple
(Negative temp)
-110
~
730
℃
-1100
~
7300
0.1
℃
1%
PT100/PT1000
-200
~
500
℃
-2000
~
5000
0.1
℃
1%
NTC50K/100K
-48
~
210
℃
-480
~
2100
0.1
℃
1%
NTC10K
-48
~
110
℃
-480
~
1100
0.1
℃
1%
Voltage
0
~
10V/0-5V/
-10
~
10V/-5
~
5V
0
~
4000
2.5mV
1%
Current Type1
0
~
20mA
0
~
4000
5uA
1%
Current Type2
4
~
20mA
0
~
4000
4uA
1%
The transmitter which is integrated inside PLC is one of the above table or mixed ones, it is up to