2.6 Analog input
This section refers to the software version query, the version number is stored in the special register
D8001, D8101, if necessary, please query the value of D8001.
Input precision of coolmay CX3G/FX3GC PLC and EX3G plc hmi all-in-one is 12-bit, directly read the
corresponded register value of each analog while using. Environment temperature is only used in
thermocouple.
2.6.1 Analog input (temperature)
Below table for software version 26210
Input signal
Range
Register value
Resolution
Accuracy
(Total Measuring range)
K-type thermocouple
0
~
1100
℃
Room temperature
~
11000
0.1
℃
1%
PT100
-200
~
350
℃
-2000
~
3500
0.1
℃
1%
NTC10K
-48
~
210
℃
-480
~
2100
0.1
℃
1%
Voltage
0
~
10V/0-5V
0
~
4000
2.5mV
1%
Current Type1
0
~
20mA
0
~
4000
5uA
1%
Current Type2
4
~
20mA
0
~
4000
4uA
1%
Below table for software version 26220
Input signal
Range
Register value
Resolution
Accuracy
(Total Measuring range)
K-type thermocouple
0
~
1100
℃
Room temperature
~
11000
0.1
℃
1%
K-type thermocouple
(Negative temp)
-210
~
1200
℃
-2100
~
12000
0.1
℃
1%
T-type thermocouple
0
~
420
℃
Room temperature
~
4200
0.1
℃
1%
T-type thermocouple
-210
~
420
℃
-2100
~
4200
0.1
℃
1%