22
COOLIUS Y50A
4.9 Refrigerant analyzer error messages
No
Error message
Description
0
ERROR 0
Contact
SERVICE CENTER
The analyzer is not working, please contact SERVICE
CENTER.
1
ERROR 1
Perform the test
again?
Unstable air or gas readings. Press
START
to try to per-
form the test again. If the message appears again, please
move the machine to another area then try again.
2
ERROR 2
Perform the test
again?
Excessively high air or gas readings. Press
START
to try
to perform the test again. If the message appears again,
please move the machine to another area then try again.
3
ERROR 3
Perform the test
again?
Air calibration failed. Press
START
to try to perform the
test again. If the message appears again, please move the
machine to another area then try again.
4
ERROR 4
Temperature
condition out of
range!
Environmental conditions out of the analyzer operating
range. Please move the machine to another area then try
again.
5
ERROR 5
Excess of air or
low refrigerant
flow.
Large amount of air in the gas sample or no refrigerant
flow. Check that the external tank valve is open.
6
ERROR 6
Air sensor expired!
Contact
SERVICE CENTER
The air sensor is expired, please contact SERVICE CEN-
TER.
7
ERROR 7
Perform the test
again or contact
SERVICE CENTER
The gas pressure is out of range, please contact SERVICE
CENTER.
17
ERROR 17
Contact
SERVICE CENTER
Refrigerant analyzer not working, contact SERVICE CEN-
TER.
Not enough pressure
for Refrigerant
Quality Test
Not enough refrigerant to perform the test.
Please check the LP and HP gauges.
No
Error message
Description
Last internal
flushing process
not completed
Internal flushing of last process was not correctly comple
-
ted.
Press
START
key to perform it again.
ATTENTION!
The following procedure is
STRONGLY DISCOURAGED! Please read
chapter 4.6 Automatic Internal flushing p. 20
and PROCEED AT YOUR OWN RISK!
NOTE:
Is possible to skip the cleaning process
by keeping pressed down the
STOP
key for 5
seconds.