Page | 22
Cool Energy inverTech Manual v6.6 2020 ©
Engineer Settings - These should be set by your installation engineer
(Altering these settings can impact system efficiency)
4.
Main Temperature Settings
Heating setp.
= Heating / Buffer Temperature
Default 45c
(Temperature of the supplied heating / buffer probe)
Cooling setp.
= Cooling / Buffer Temperature
Default 12c
(Temperature of the supplied heating / buffer probe)
Hotwater setp.
= Hot Water Temperature
Default 50c
(Temperature of the supplied hot water probe)
5.
Differential Temperature Settings:
Hotwater setp.
Temp. diff.
=
(Default 5c)
(Temperature differential before restart)
Stop temp diff. =
(Default 0c)
(Buffer range to optimise compressor frequency)
Cool water setp.
Temp. diff.
=
(Default 5c)
(Temperature differential before restart)
Stop temp diff. =
(Default 2c)
(Buffer range to optimise compressor frequency)
6.
PID Settings:
Kp.
=
(Default 5c)
(Proportional control of frequency adjustment)
Содержание inverTech CE-iVT18
Страница 10: ...Page 10 Cool Energy inverTech Manual v6 6 2020 Example Installation Method 2 Heating only with radiators ...
Страница 12: ...Page 12 Cool Energy inverTech Manual v6 6 2020 Example Installation Method 4 Hot Water Thermal Store Only ...
Страница 13: ...Page 13 Cool Energy inverTech Manual v6 6 2020 Example Installation Method 5 Hot Water Heating ...
Страница 16: ...Page 16 Cool Energy inverTech Manual v6 6 2020 Wiring Diagrams Single Phase inverTech Models ...
Страница 17: ...Page 17 Cool Energy inverTech Manual v6 6 2020 3 Phase inverTech Models ...
Страница 37: ...www coolenergyshop com www heatingshop ie ...