.CLEVELAND RANGE Mini Combi
For
TIM HORTENS
SEQUENCE OF OPERATIONS
When using these instructions refer to the
included
wiring schematic.
1
When incoming power (220 VAC) is connected to the combi, 220 VAC is sent
a
To the normally open contacts of the Safety Contactor (K0)
b
Through the 3A fuse (F1.1) to
•
The 12 vdc power supply (G1)
◊
12vdc is sent to terminals 1 and 2 of the Easy Touch Power Switch
◊
12vdc is sent to Terminal 10 of connector X13 on the Control Board
(A10)
•
Through the oven high limit (B7) and another 3 amp fuse (F10), to terminal 1
of the connector X12 on the control Board (A10).
c
With 12 VDC to the Control Board (A10), the Operation Board (A11) is
energized
2
When the ON/OFF is depressed 12VDC is sent from terminal 3 and 4 of the on/Off
switch to to terminals 3 and 4 of Connector X10
a
The display will show Easy Touch and the Tim Hortons.
b
12 VDC is sent from terminals 1 and 2 of connector X10 on the control Board
(A10) to the cooling fans (M3.1 and M3.2)
c
12VDC is sent from terminal 9 of connector X13 on the Control Board (A10) to
energize the Humidity Valve Motor (M2)
•
As the Humidity Valve Motor rotates 360 degrees the cam switch (S2) opens
and closes to set the position of the cam on the motor.
d
220 VAC is sent from terminal 5 of connector X12 of the control Board to the
Condenser Valve (Y1) for 30 seconds.
e
220 VAC is sent from terminal 2 of X13 on the Control Board to the coil of the
Safety Contactor (K0).
•
220 VAC is sent to the normally open contacts of the element contactor (K4).
•
220 VAC is sent to the AC Drive terminals L1 and L2
3
With the combi in the steam mode with time on the timer the door closed and the start
icon is depressed
a
The front display will include a Thermometer while the unit preheats.
b
The fan circuit is energized
•
Voltage is sent from terminals 7 and 9 on connector X14 on the Control Board
to the terminals S and R respectively on the AC drive board for 2 minutes.
◊
The AC drive board ramps up the oven fan motor (M1) Clock wise for 2
minutes.
•
Voltage is removed from the AC Drive for 15 Seconds
•
Voltage is sent from terminals 7 and 8 on connector X14 on the Control Board
to terminals S and F respectively on the AC drive board for 2 minutes.
62
Содержание Mini Combi with Easy Touch
Страница 43: ...42 BACK PANEL ASSEMBLY...
Страница 44: ...43...
Страница 45: ...44 SINGLE WATER VALVE ASSEMBLY...
Страница 46: ...45 DOUBLE WATER VALVE ASSEMBLY...
Страница 47: ...46 TIM HORTONS CONTROL PANEL Before S N 1110230000900...
Страница 48: ...47 TIM HORTONS CONTROL PANEL After S N 1110 2300 00900...
Страница 49: ...47 48 C5118285 ELECTRICAL PANEL ASSEMBLY...
Страница 50: ...49 5 WIRE INSERTION VIEW A10 X16 6 CONTROL RELAY BOARD...
Страница 51: ...50 TRIM POTS ARE TO BE SET AS SHOWN AC DRIVE BOARD Wire Harness for motor 300772...
Страница 52: ...51 OES 6 10 Mini R H Door Assembly C2529771 RH C2527089...
Страница 53: ...52 Left Hand Door Assembly C2529775...
Страница 54: ...53 FAN MOTOR ASSEMBLY 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 16 18...
Страница 55: ...54 CONDENSATE BOX 1 2 3 4 6 7 5 8 9 10 11 12 13...
Страница 57: ...56 OES 6 10 MINI LIGHT ASSEMBLY...
Страница 58: ...57 CLEANING PUMP ASSEMBLY...
Страница 59: ...58...
Страница 60: ...59...
Страница 61: ...60...
Страница 62: ...61...