8) Sender Configuration
Allows the user or OEM to set up the proper sender types and engine safety limits of the module. Options
include the following. Defaults in
[ ].
8.1
Press & Temp Units
–
Metric,
[English]
8.2
Sender Check Bypass
–
5
– 60 Sec,
[10]
8.3
Fuel Sender
– VDO,
[S-W]
8.4
Fuel Level Check
– Never, Always,
[Run]
8.5
Low Fuel Prealarm
– 0-100%
[20]
8.6
Low Fuel Alarm
– 0-100%
[1%]
8.7
Fuel Alarm Delay-
0
– 100 Sec,
[5]
8.8
Low Oil Press Check
– Never, Always,
[Run]
8.9
Low Oil Press Prealarm
– 0-100 PSI
[15]
8.10
Low Oil Press Alarm
– 0-100 PSI
[10]
8.11
Oil Press Alarm Delay-
0
– 100 Sec,
[5]
8.12
Temp Check
– Never, Always,
[Run]
8.13
Low Temp Prealarm
– 0 - 300 F
[0]
8.14
Low Temp Alarm
– – 0 - 300 F
[0]
8.15
High Temp Prealarm
– 0 - 300 F
[220]
8.16
High Temp Alarm
– – 0 - 300 F
[230]
8.17
Temp Alarm Delay-
0
– 100 Sec,
[5]
8.18
Battery Volts Check
– [Never]
, Always, Run
8.19
Low Bat Prealarm
– 0.0 – 40.0 VDC
[12.0]
8.20
Low Bat Alarm
– 0.0 – 40.0 VDC
[0.0]
8.21
High Bat Prealarm
- 0.0
– 40.0 VDC
[15.0]
8.22
High Bat Alarm
– 0.0 – 40.0 VDC
[40.0]
8.23
Bat Alarm Delay-
0
– 100 Sec,
[5]
8.24
Over Speed Check
–
[Never]
, Always, Run
8.25
Over Speed Alarm
– 0-5000 PSI
[3000]
9) Calibration
Allows the user or OEM to trim specific parameters of the module. Defaults in
[ ].
9.1
Battery Trim
–
0-1000mV,
[500mV]
9.2
Flywheel Teeth
–
1-200,
[100]
9.3
Auto Set Teeth?
-Yes,