background image

Terminal unit and
zone valve actuators

Rev. a

  03/04

          1

DBL157E

ISO 9000

CONTROLLI

MVT

CONTROLLI Division

16010 SANT’OLCESE Genova - Italy

Tel.: +39 01073061

Fax: +39 0107306870/871

E-mail: [email protected]

Web: www.controlli.org

APPLICATION

MVT actuator is designed to provide, with V.T and V.BT valve
bodies, floating control of hot/cool water in two/four-pipe fan-
coil units, zone and solar plants, reheat coils and dehumidifi-
cation batteries.

ACCESSORIES

MVT44C1  Cable for MVT441  3-wire 1,5 m (CEI 20-22/II)

N4149

OPERATION

POSSIBLE COMBINATIONS AND
CONNECTIONS

MVT actuators are to be used with CONTROLLI VST, VMT, VTT,
VSBT, VMBT valves.
The MVT4. series can be connected to any 3-position control-
ler, with characteristics corresponding to details included in
the paragraph “TECHNICAL CHARACTERISTICS”.
The MVT5. series is standard proportional as indicated on table
1.
Due to the presence of the magnetic clutch, the actuator could
be continuously powered up without damages but, for life in-
crease and energy saving, it is highly reccomended to use a
controller equipped with a cut-off function (suggested timing
120% of stroke time).

MANUFACTURING CHARACTERISTICS

The actuator consists of a base and a housing made of syntetic
materials which contain motor, gear box, magnetic coupling,
valve driving screw spindle.
A ring nut M30x1.5 is placed on the lower part; it allows an easy
coupling to the valve without special tools.
The actuator is equipped with a cable for 3-wire electrical con-
nection. It requires no maintenance.

TECHNICAL CHARACTERISTICS

Power supply

24 V ~ + 10%

Consumption

0,5 VA  (MVT4.)
1 VA     (MVT5.)

Frequence

50/60  Hz

Stroke timing

100 s for V.T valves having
5,5 mm stroke (at 50 Hz)

Speed

18 s/mm at 50 Hz - 15 s/mm
at 60 Hz

Force

200 N (UNI 9497)

Stroke

6,5 mm

Temperature:
  - working

-5T55    °C

  - storage

-25T65  °C

Protection class

III  (IEC 950)

Connecting cable

3-wire 1,5 m (CEI 20-22/II)

Protection degree

IP43 CEI EN 60529

Weight

0,2 Kg.

The product conforms to EMC 89/336 directive with
reference to the below-mentioned standards:
for emission EN 50081-1       for immunity EN 50082-1

INSTALLATION AND MOUNTING

The actuator can be mounted in the positions indicated below.
Before assembling the actuator to the valve, remove the pro-
tection cap from valve and make sure that the actuator screw
spindle corresponds to the upper notch on the base plate (fac-
tory supplied position). Otherwise, it is advisable to consider
that, in order to mount the actuator on the valve correctly, the
force of the valve internal spring will have to be overcome.Then
it should be fixed by tightening the M30X1,5 ring nut on the
thread located on the valve body (Fig. 1).

Mounting positions allowed

MVT actuator is electric bidirectional.
The valve stem movement is produced by rotation of a screw
spindle connected, through a gear train, to a synchronous bidi-
rectional motor.
An internal magnetic hysteresis coupling limits the torque on
the valve stem, avoiding the usage of microswitches and pro-
tecting the actuator from overload.

PART

NUMBER

CONTROL SIGNAL

POWER SUPPLY

MV T44

3 position

MVT441

3 position

w ithout cable

MV T56

proportional

0…10/6…10/1…5/2…10

4…7/6…9/8…11V-

MV T57

proportional

0…10V-

MVT56A

proportional

4÷20 mA

24 V~

TABLE 1

N4038

Perform the electrical connections in compliance with existing
rules (Fig. 2)
Through the slits located by the ring nut, it is possible to  ob-
serve the valve stem movement.
With 24 V~ voltage between 

w

hite (common) and brown the

actuator lowers the valve stem, between white  (common) and
green the actuator lifts the valve stem.