Dip
switch
OFF
ON
1
Direct Action
Reverse Action
2
Modulating Control (MOD) (Input between Y [+] and M [-])
3 point floating (INC) ( Y1 open-extend , Y2 close-retract
connected to M)
3
-
Selection of sequence mode, control range defined by DIP
n. 5
4
Modulating Control 0-10Vdc
(DIP n. 2 OFF only)
Modulating Control 2-10Vdc
(DIP n. 2 OFF only)
5
Sequence Control 0-5Vdc with DIP n. 4 OFF only
Sequence Control 2-6Vdc with DIP n. 4 ON only
(DIP n. 3 ON only)
Sequence Control 5-10Vdc with DIP n. 4 OFF only
Sequence Control 6-10Vdc with DIP n. 4 ON only
(DIP n. 3 ON only)
6
Voltage Input Signal Vdc
(input between Y [+] and M [-])
Current Input Signal 4-20mA
(input between Y [+] and M [-]). In this case DIP n. 4 must be
set to ON.
7
Automatic Calibration: the actuator updates the stroke range if
an unexpected mechanical stop is detected for at least 10s
Manual Calibration: the actuator calibration is started
moving the DIP from OFF to ON or vice versa. With DIP in
ON in case of extra stroke or if an unexpected endpoint is
detected, the actuator will never update the stroke
U=10V
Y1
Y2
U = 10V
U = 2V
U= feedback
U= feedback
U = 2V
Factory settings
Jumper for emergency re-
turn position selection (open
jumper - totally retracted
joint; closed jumper - totally
extended joint)
RED LED (ultraca-
pacitors status)
GREEN LED (ultra-
capacitors status)
Ultracapacitors
open jumper
-
retracted joint
closed jumper
-
extended joint
DIP SWITCHES AND JUMPER SETTINGS
Set the DIP switches according to the tables here below. In order to be sure that any modification has been accepted by the actuator,
power down and power it up again or act on the manual operation handle.
1
st
Issue rev. b
04/2016
DBL462e
Page 5