background image

Dip 

switch

OFF

ON

1

Direct Action

Reverse Action

2

Modulating Control (MOD) (Input between Y [+] and M [-])

3 point floating (INC) ( Y1 open-extend , Y2 close-retract 

connected to M)

3

-

Selection of sequence mode, control range defined by DIP 

n. 5

4

Modulating Control 0-10Vdc

 

(DIP n. 2 OFF only)

Modulating Control 2-10Vdc

 

(DIP n. 2 OFF only)

5

Sequence Control 0-5Vdc  with DIP n. 4 OFF only

 

Sequence Control 2-6Vdc  with DIP n. 4 ON only

 

(DIP n. 3 ON only)

Sequence Control 5-10Vdc  with DIP n. 4 OFF only

 

Sequence Control 6-10Vdc  with DIP n. 4 ON only

 

(DIP n. 3 ON only)

6

Voltage Input Signal Vdc

 

(input between Y [+] and M [-])

Current Input Signal 4-20mA 

 

(input between Y [+] and M [-]). In this case DIP n. 4 must be 

set to ON.

7

Automatic Calibration: the actuator updates the stroke range if 

an unexpected mechanical stop is detected for at least 10s

Manual Calibration: the actuator calibration is started 

moving the DIP from OFF to ON or vice versa. With DIP in 

ON in case of extra stroke or if an unexpected endpoint is 

detected, the actuator will never update the stroke 

U=10V

Y1

Y2

U = 10V

U = 2V

U= feedback

U= feedback

U = 2V

Factory settings

Jumper  for  emergency  re-

turn position selection (open 

jumper  -  totally  retracted 

joint;  closed  jumper  -  totally 

extended joint)

RED  LED  (ultraca-

pacitors status)

GREEN  LED  (ultra-

capacitors status)

Ultracapacitors

open jumper

-

retracted joint

closed jumper

-

extended joint

DIP SWITCHES AND JUMPER SETTINGS

Set the DIP switches according to the tables here below. In order to be sure that any modification has been accepted by the actuator, 

power down and power it up again or act on the manual operation handle.

1

st

 Issue rev. b

04/2016

DBL462e

Page 5

Содержание MVE2R Series

Страница 1: ...apacitors charging phase look at table on page 7 During this phase all the functions of the actuator are inhibited and the charge status of the ultracapacitors is signalled through 2 LEDs look at para...

Страница 2: ...uator link loose voltage supply out of range These faulty conditions are signalled via the GREEN and RED LED on the lower electronic board blinking accordingly see Diagnostic Alarm Function Table Cont...

Страница 3: ...red 2TGB F 3TGB F PN16 not required Controlli valves with threaded M40 connections except for VSB VMB VSBF VMBF PN16 AG51 VSB VMB VSBF VMBF PN16 AG52 AG63 Other manufacturers Siemens AG70 10 AG70 14 D...

Страница 4: ...mon SAFETY PRESCRIPTIONS 230 V products Install on the power supply line a protecting device to avoid short circuits fuse or magneto thermic according to the spec ifications in force in case of accide...

Страница 5: ...updates the stroke range if an unexpected mechanical stop is detected for at least 10s Manual Calibration the actuator calibration is started moving the DIP from OFF to ON or vice versa With DIP in ON...

Страница 6: ...ack to the initial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove...

Страница 7: ...aviour Actuator status 1 GREEN ON The actuator arrived at the extreme point of the stroke 2 GREEN BLINKING The actuator is moving or arrived at the intermediate point of the stroke 3 RED GREEN BLINKIN...

Отзывы: