TERMINAL BLOCK

230~V ±10%

*

F

N

U Y M Y1 Y2

Floting only sink (connect Y1, Y2 to M)

*

(*) In order to use the floating control the only possible connection is 

between terminal M and Y1/Y2. Do not connect Y1/Y2 to phase 

(F) or neutral (N).

Label

Description

Function

Wire Size 

Max wire 

Length

F

230Vac

Power 

Supply

AWG16

 

(min 1mm

max 1.5mm

2

)

75m

N

Y

0..10Vdc

Modulating 

Control 

Input

AWG20

 

(min 0.5mm

2

 - 

max 1.5mm

2

)

200m

M

0V (Common)

Y1

Open

Floating 

Control 

Input

AWG20

 

(min 0.5mm

2

 - 

max 1.5mm

2

)

200m

Y2

Close

V+

16 Vdc

Voltage 

Output 

(max 25mA)

AWG20

 

(min 0.5mm

2

 - 

max 1.5mm

2

)

200m

M

0V (Common)

U

2÷10Vdc

Feedback 

Output 

Signal

AWG20

 

(min 0.5mm

2

 - 

max 1.5mm

2

)

200m

M

0V (Common)

SAFETY PRESCRIPTIONS

230 V products

 

• 

Install  on  the  power  supply  line  a  protecting  device  to  avoid 

short circuits (fuse or magneto-thermic) according to the spec-

ifications in force;

• 

in case of accidental removal of the cover to make sure that 

power is disconnected before working on the actuator or near it;

• 

the products are maintenance free.

WIRING DIAGRAMS

230Vac

3-point Floating Control

Controller

Open
Close

MVE

Y2

Y1 F

M

N

Neutral

Modulating Control (0-10Vcc)

230Vac

Controller

C
Command -

MVE

M

Y

F

N

Neutral

Note:   To avoid damages to electronic components caused by the 

PCB bending, do not press too much while fixing the terminal 

block.

GROUND CONNECTIONS

Connect the ground terminal to the proper screw labelled with the 

ground symbol as shown in the picture here below.

 

ground terminal

1

st

 Issue rev. b

04/2016

DBL462e

Page 4

Содержание MVE2R Series

Страница 1: ...apacitors charging phase look at table on page 7 During this phase all the functions of the actuator are inhibited and the charge status of the ultracapacitors is signalled through 2 LEDs look at para...

Страница 2: ...uator link loose voltage supply out of range These faulty conditions are signalled via the GREEN and RED LED on the lower electronic board blinking accordingly see Diagnostic Alarm Function Table Cont...

Страница 3: ...red 2TGB F 3TGB F PN16 not required Controlli valves with threaded M40 connections except for VSB VMB VSBF VMBF PN16 AG51 VSB VMB VSBF VMBF PN16 AG52 AG63 Other manufacturers Siemens AG70 10 AG70 14 D...

Страница 4: ...mon SAFETY PRESCRIPTIONS 230 V products Install on the power supply line a protecting device to avoid short circuits fuse or magneto thermic according to the spec ifications in force in case of accide...

Страница 5: ...updates the stroke range if an unexpected mechanical stop is detected for at least 10s Manual Calibration the actuator calibration is started moving the DIP from OFF to ON or vice versa With DIP in ON...

Страница 6: ...ack to the initial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove...

Страница 7: ...aviour Actuator status 1 GREEN ON The actuator arrived at the extreme point of the stroke 2 GREEN BLINKING The actuator is moving or arrived at the intermediate point of the stroke 3 RED GREEN BLINKIN...

Отзывы: