Modbus TCP Module
Operation
8
Operation
The Modbus TCP Module must be controlled by a Modbus client (such as a PLC) which
complies with the Modbus Protocol Specification. For successful operation, the client must
also support all functions and interfaces described in this document.
8.1 Device Classification
The Modbus TCP Module is a Modbus server and must be managed by a Modbus client
over Ethernet.
8.2 Ensuring Safe and Successful Control
Data written to the device will remain in its registers until the data is overwritten or the
device is reinitialised. The device will not transfer successive duplicate commands to the
soft starter.
•
If the soft starter is started via fieldbus communications but stopped via the keypad
or a remote input, an identical start command cannot be used to restart the starter.
•
If the soft starter may also be controlled via the keypad or the remote inputs (as well
as via fieldbus communications), a control command should be immediately
followed by a status query to confirm the command has been actioned.
9
Modbus Registers
NOTE
All references to registers mean the registers within the module unless otherwise
stated.
9.1 Standard Mode
Command and Configuration Registers (Read/Write)
Register Description
Bits
Details
40001
Command
(single write)
0 to 3 To send a command to the starter, write the
required value:
00000000 = Stop
00000001 = Start
00000010 = Reset
00000100 = Quick stop (coast to stop)
00001000 = Forced communication trip
4 to 14
Reserved
15
Must = 1
40002
Reserved
40003
Reserved
40004
Reserved
40005
Reserved
40006
Reserved
40007
Reserved
40008
Reserved
40009
Reserved