28
M’Ax Installation Guide
www.controltechniques.com
Issue Number: 6
B.2
Optional RFI filter data
Main ratings
Maximum ambient temperature at rated current and frequency range:
50°C (122°F)
Ingress protection: IP20
AC supply ratings
Maximum operating voltage: 480V at up to 50°C (122°F)
AC supply frequency: 48 to 62 Hz
Ground leakage current
Ground-leakage current phase-to-phase and phases-to-ground is as
follows:
Balanced supply, all phases present: 33mA
Two phases disconnected: 192mA
These figures apply for an AC supply of 400V at 50Hz. For other AC
supply voltages and currents, scale the values of leakage current
proportionally.
Discharge resistors
330K
Ω
star network between the AC supply phases; the star point is
connected by a 1M
Ω
resistor to ground. These resistors are fitted
internally.
Maximum current overload
150% of rated current for 60 seconds.
RFI Filter Overall dimensions
* Dimensions when attached to drive
Part number
4200-1645
4200-0081
Max. continuous current
16A
16.5A
Power dissipation at rated current
6W
6W
CT Part
Number
Schaffner
Part Number
Dimension
Weight
Height
Width
Depth
kg
lb oz
4200-1645
FN3258-16-45
250mm
9.842in
45mm
1.772in
70mm
2.776in
0.8
1lb12oz
4200-0081
FS-5599-16-5-07*
360mm
14.173in
54.5mm
2.145in
287mm
114.299in
1.4
3lb1oz