EMS-96
Instruction Manual
IM1200-U v1.6
Pag. 47 / 48
Dimensions
For fixing the flush mount version instrument to the panel,
use the fixing devices supplied, by inserting them in the side
groves of the enclosure and tighten the screws.
For safety reasons, place an external fuse protection at the
input voltages, and use adequate cables for the working
voltages and currents, with a section from 0.5 to 2.5 mm
2
.
Technical features
Auxiliary power supply
Voltage range
90÷250 Vac/dc
20÷60 Vac/dc
Frequency range
50/60 Hz
Protection fuse
1A Time Lag
Power consumption
8VA max – 1VA min (depending on the options and activities)
Measures / precision
Energy
Factory Default: CEI EN 62053-21 compliant – Class 1 (1%)
CEI EN 62053-22 compliant – Class 0.5 S (0.5%)
CEI EN 62053-22 compliant – Class 0.2 S (0.2%)
Frequency
40÷70 Hz
Power factor
± 1.000
Cos
± 1.000
Tan
± tan 89.9°
THD
IEC62053-22 Compliant
Harmonics
Up to 20
th
Harmonics – IEC62053-22
Refresh rate
Once per second (all measures)
Measurement range
Voltage
30÷400VAc phase to neutral (52÷693 Vac phase to phase)
Current 1A
10mA÷1A (for 1, 0.5S or 0.2S Class accuracy, depending on the option)
Current 5A
50mA÷5A (for 1, 0.5S or 0.2S Class accuracy, depending on the option)
Installation
Distribution
networks
low
and
medium
voltage
-
single
phase
connection
-
three
phase
with
neutral
-
three
phase
without
neutral
Voltage
inputs
Inputs type
3 phase Neutral
Permitted over voltage
480 Vac phase to neutral (830Vac continuous phase to phase)
Over-voltage category: III (permanent installations)
Input resistance
>1.8M
Frequency range
50/60 Hz
Note: V1 terminal must be connected
Load (Burden) for each input
0.09 VA
Current inputs
Inputs type
3 inputs isolated by internal current transformers
additional input for neutral current with the same characteristics to the phase inputs
Maximum continuous overload 1A
1.3A
Maximum continuous overload 5A
6.5A
Load (Burden) for each input
0.00055 VA
MAX
Mechanical
Overall dimension
96x96x130 mm
Weight
450 gr
Environment conditions
Operating temperature
-10… +60°C
Storing temperature
-15… +70°C
Communication RS485
Protocol
Modbus RTU
96
9
6
9.8
100
8
9
.5
10
12