EMS-96
Instruction Manual
IM1200-U v1.6
Pag. 40 / 48
Example of setting (in the correct order) to set an alarm when the voltage exceed 230V on the phases 1, 2 and 3 (V1
AND
V2
AND
V3) with
saving the event and the switching of a digital output when the alarm is present and when it disappear.
SETPOINT 1
(primary)
Source
: Internal measures
Group
: instant
Item
: V1
High threshold
: 230
High threshold unit
: V
Over debounce
: 10 (sec.)
Logic operation over
: AND
Operands 1-16
:
-
Setpoint 2
: yes
-
Setpoint 3
: yes
Action over
:
-
save event
: yes
-
DO change
: yes
Action entry
:
-
save event
: yes
-
DO change
: yes
DO used
:
-
DO-1
: yes
Enable
: yes
SETPOINT 2
(secondary)
Source
: Internal measures
Group
: instant
Item
: V2
High threshold
: 230
High threshold unit
: V
Over debounce
: 10 (sec.)
Enable
: yes
SETPOINT 3
(secondary)
Source
: Internal measures
Group
: instant
Item
: V3
High threshold
: 230
High threshold unit
: V
Over debounce
: 10 (sec.)
Enable
: yes
Threeshold
Thrend
Measure
Sec
Sec
Sec
Threeshold
Threeshold
Debounce
Debounce
Debounce
State Set Point 1
State Set Point 2
State Set Point 3
DO ACTION
V1
V2
V3