EMS-96
Instruction Manual
IM1200-U v1.6
Pag. 34 / 48
Communication
Setup
Communication
COM1/2
Setting
COM1/2 setting (option)
Range
Default
Mode
Slave / Master
Slave
Slaves to read
1 ÷ 20
1
Number of slave connected in master mode.
Master Timeout [ms]
0 ÷ 10000
800
Time after than it will be set the no slave response flag and increase the NO RESPONSE COUNTER if the answer isn’t received
(Master Mode).
Scan rate [ms]
0 ÷ 10000
1000
Delay between two master request (Master mode).
Note:
this value must be greater than TIMEOUT.
Node address
1 ÷ 247
1
Instrument identifier on the modbus network.
Note:
valid only in Slave Mode.
Baud rate [kbit/s]
4800 / 9600 / 19200 / 38400 / 57600 / 115200
38400
The communication speed.
Stop bits
1 / 2 stop
1 stop
Communication parameters.
Parity
None / Odd / Even
None
Communication parameters.
Min. response delay [ms]
5 ÷ 100
10
Modify this value if use a slow external converter.
Setup
Communication
COM1/2
Slave tipology
COM1/2 Slave read (option)
Range
Default
Slave node 1
TTC-V
/
CTT-4
/
CTT-8
/
HRI
/
EMM-h
/
EMT-4s
/
EMS-96
/
RI-SM
---
Type of slave (instrument) connected to the address 1.
………………..
………………..
Slave node 20
TTC-V
/
CTT-4
/
CTT-8
/
HRI
/
EMM-h
/
EMT-4s
/
EMS-96
/
RI-SM
---
Type of slave (instrument) connected to the address 20.
Note: Accessible only with COM in master mode. The number of slave node is equal of the value set in “
Slave to read
”.
Setup
Communication
COM1/2
Slave name
COM1/2 Editing Slaves name (option)
Range
Default
Slave node 1
Slave 1
Edit the name of the slave.
………………..
………………..
Slave node 20
Slave 20
Edit the name of the slave.
Note: Accessible only with COM in master mode.
Setup
Communication
Profibus
Profibus (option)
Range
Default
Address [node]
1 ÷ 126
1
Instrument identifier on the profibus network.