Step
Display
Description
Text
Ref
If non-linearity correction is to be programmed, up to 10 frequencies
and scaling factors can be entered.
Freq 1
Freq1 is programmed to the first frequency point
in the range of 0 to 9999Hz.
3.6
Fact 1
This is the K-factor of the flowmeter (ie. pulses
per gal, etc) at Freq1. The digits before the
decimal point (whole numbers) are programmed
first, followed by the decimals. The scaling factor
can be programmed in the range of 0.1000 to
50,000.
Freq2
Freq2 is programmed to the second frequency
point. If any Freq is set to 0, no further correction
points can be programmed and the non-linearity
correction is limited to that number of points.
Fact 2
Scaling Factor 2.
to
Fact 10
Scaling Factor 10. Note that Freq10 is not
displayed since it must always be zero.
6
F dPt
Number of decimal points with which the Rate is
to be displayed between 0 to 0.00000.
7
t.base
The Timebase with which the Rate is calculated
must be entered as:
60secs
hours
days
secs
units/min
units/hour
units/day
units/second
Calibration 35