background image

W415-1112 / 06.12.12

49

 

○ Control of the secondary heat source (either electric or oil) is done by a combination of a selector switch 

on the main furnace control panel and a second thermostat located beside and at the same height as the 

wood furnace thermostat.  The selector toggle switch needs to be switched  to the appropriate back up 

furnace installed (can be switched to either oil or electric depending on energy rates if both backups are 

installed).  The thermostat for the back up heat source should be set 4°f to 5°f (2°C to 3°C) below the 

setting for the wood thermostat.  Thus once the heat from the wood section starts to decline, the corre-

sponding decline in room temperature will cause the second thermostat to call heat from the secondary 

heat source.  note that interlocks in the control system will force the secondary heat source to shut down if 

the temperature in the supply plenum of the wood furnace exceeds the set value of the "High limit" switch 

(250°f) (121°C).

NOTE

The control of the "add on" style installation is the same as the fore mentioned paragraph except for the 

position of the selector toggle switch being redundant.

BOTH OIL AND ELECTRIC FURNACES HAvE RESET CONTROLS AND pROCEDURES REqUIRED TO 

RESTART THE UNITS IF A FAULT HAS BEEN DETECTED AND UNITS LOCkED OUT.  ONLY A qUALI-

FIED INSTALLER/SERvICE pERSON SHALL pERFORM THESE RESET pROCEDURES AS A CAUSE 

AND REpAIR MUST BE DETERMINED BEFORE THE UNIT CAN BE RESTARTED.  FAILURE TO FOL-

LOW THIS STEp COULD RESULT IN pROpERTY DAMAgE, INjURY OR DEATH.

SERvICE pERSONS CAN FIND TROUBLESHOOTINg AND RESET pROCEDURE IN THE MANUALS 

ACCOMpANYINg BOTH THE ELECTRIC FURNACE AND OIL BURNER MODULES.

 

○ a summer fan switch has been added to the main electric control box.  This will provide low speed air 

circulation during the summer time when the furnace is not being used.  depress rocker switch to “Summer 

fan” position, the switch will light and the fan will run.

ENSURE THE SUMMER SWITCH REMAINS IN THE "OFF" pOSITION DURINg THE HEATINg SEASON.  

FAILURE TO COMpLY WITH THIS WILL RESULT IN ExCESSIvE CHILLINg OF THE ExHAUST pROD-

UCTS AS THEY pASS THROUgH THE ExCHANgER pIpES, THE FURNACE FLUE AND THE CHIMNEY 

SYSTEM.  THIS CHILLINg WILL RESULT IN THE CONDENSATION OF ExHAUST pRODUCTS IN THE 

ExCHANgER AND CHIMNEY RESULTINg IN CREOSOTE BUILD Up.  THE CREOSOTE BUILD Up WILL 

RESULT IN REDUCED EFFICIENCIES OF THE ExCHANgER TUBES AND SUBSTANTIALLY INCREAS-

ES THE RISk OF A CHIMNEY FIRE.

expansion / contraction noises during heating up and cooling down cycles are normal and to be expected.

When first installed, the furnace brick and metal are cold and must become hot before the appliance will func-

tion well. during the break-in period (the first 2 or 3 fires) create only small, hot fires using kindling; this will 

allow the firebrick to cure. do not be alarmed if small hairline cracks develop in the firebrick. This is a normal 

occurrence and does not  pose a safety hazard. The paint may also smell a little for the first few fires as it 

cures and you may wish to open a door or window to alleviate the smell.

There are many different ways to start a fire, review the hints and warnings in this section to ensure the fire is 

started properly.

8.2  CONTrOL SySTEm - SECONdAry FurNACE "Add ON", "wOOd/OIL", 

"wOOd/ELECTrIC", "wOOd/OIL/ELECTrIC" CONFIGurATIONS

8.3  CONTrOL SySTEm - SummEr FAN

8.4  OPErATING SOuNdS ANd SmELLS

Содержание CHMF150

Страница 1: ...contact the local building or fire or other authority having jurisdiction and follow their guidelines Operate only with the doors tightly closed Do not use an elevated grate or otherwise raise the fir...

Страница 2: ...e to combustibles 39 6 3 1 CHMF150 shielding specifications 39 6 4 flue configuration for add on furnace configuration 40 6 5 connecting ductwork plenums between add on furnace and original furnace 40...

Страница 3: ...tion Read through these instruc tions thoroughly before starting your installation and follow them carefully throughout your project HEAT EXCHANGER Section 9 8 1 BLOWER MODULE Section 5 2 BYPASS DAMPE...

Страница 4: ...nd free from combustible materials gasoline and other flammable vapors and liquids under no circumstances should this appliance be modified do not use this appliance if any part has been under water i...

Страница 5: ...ts must be kept from touching the appliance when it is hot contact your local authorized dealer distributor for safety screens that may be available for this product combustible material such as firew...

Страница 6: ...W415 1112 06 12 12 6 AIR FLOW CIRCULATION AND HEAT TRANSFER COMBUSTION AIR FLOW...

Страница 7: ...omatic control with thermostat Large firebox capacity Outside air for combustion Choice of glass door for radiant heat through front of furnace or solid door to provide more heating through exchange s...

Страница 8: ...e spillage can also set off smoke alarms negative pressure within your home may inadvertently affect your appliance exhaust fans such as bathroom fans range hoods and clothes dryers can strongly influ...

Страница 9: ...that more than one fuel burning furnace in a multi furnace configuration may operate at the same time The 4 102 mm inlet can also draw combustion air from the room provided adequate make up air is av...

Страница 10: ...fs and Hardware the base pallet is secured to the furnace BY ADJUSTING the LEGS AT the BOTTOM OF the FURNACE THE BASE PALLET SHOULD NOT BE REMOVED UNTIL THE FURNACE IS PLACED CLOSE TO ITS FINAL Instal...

Страница 11: ...o the weight tipping the skid step 2 Firmly support side of the furnace near top to prevent furnace toppling when the skid furnace are tilted high centre of gravity 2ND Installer supports weight of un...

Страница 12: ...ding side panels step 3 Switch panels to opposite sides and reverse process Attach the electrical mounting brackets with fasteners supplied Line up the bracket mounting holes in the bracket and furnac...

Страница 13: ...BRACKET CAN BE ADJUSTED c With shutter plate pushed towards the front of the furnace in the air damper assembly slot and the base of the VGB held firmly down on the top of the air supply chamber posi...

Страница 14: ...es in conjunction with the compressed vermiculite baffles will need to be installed as follows note The holes in the tubes must face to front of furnace 2 Assemble the control box as illustrated using...

Страница 15: ...to ensure there are not gaps as illustrated 2 step 2a tube locator bracket style installation Insert tab of stainless steel tube locator bracket into left most hole of the secondary air tube Secure th...

Страница 16: ...W415 1112 06 12 12 16 DOOR HANDLE DOOR SPRING WASHER SPACER DOOR HANDLE LATCH LOCK WASHER NUT NOTE Position of door handle latch front view door handle configuration 4 8 DOOR HANDLE INSTALLATION...

Страница 17: ...3 Hybrid CHMF150 200 as a Combination Wood Electric Furnace see Section 5 4 Hybrid CHMF150 200 as a Combination Wood Oil Electric Furnace see Section 5 5 5 0 CONFIGURATION OF LEFT AND RIGHT Return Air...

Страница 18: ...ce installation 6 Maintain sufficient combustion air supply to both furnaces Air starvation is dangerous see Section 3 2 Outside Combustion Air 7 Refer to manufacturer s instruction of existing furnac...

Страница 19: ...blower 14 Do not connect under any circumstances to the chimney or vent serving a gas furnace or gas appliance 15 Disconnect power from both electric furnace and Add On furnace before servicing 16 Re...

Страница 20: ...return air configuration Locate the wood limit switch bracket on the furnace top next to the plenum by lining up the clearance holes in the lower switch bracket and the pilot holes in the furnace top...

Страница 21: ...control will affect the operating efficiency of the furnace and will void the warranty coverage Once set point limits have been confirmed carefully manipulate wiring inside wood limit connection box s...

Страница 22: ...when operating Add On should provide an airflow of 1100 1300 CFM thru the ducting system CHMF150 1300 1700 CFM CHMF200 note Instructions and specifications to be included in kit for a ECM motor in or...

Страница 23: ...st the levelling legs on the blower box mod ule so that the module is level and clearance hole on the mounting flanges align with pilot holes on side of the furnace panel step 7 Lift the blower outlet...

Страница 24: ...lure to comply may result in electric shock fire property damage or person aL INJURY step 10 See SECTION 7 0 ELECTRICAL CONNECTIONS AND SCHEMATICS step 9 See SECTION 6 0 PLENUM AND VENTING INSTALLATIO...

Страница 25: ...0 Remove the contents of the Oil Burner Module Kit HMFK OFRF40 or HMFK OFBNX and compare with the contents list on the Manual Addendum accompanying the Oil Furnace Module step 11 Remove 6 hex head scr...

Страница 26: ...y damage AIR FLOW DIRECTION FROM BLOWER MODULE HEAT EXCHANGER COMBUSTION CHAMBER AIR FLOW DIRECTION FROM BLOWER MODULE HEAT EXCHANGER COMBUSTION CHAMBER LEFT HAND RA CONFIGURATION RIGHT HAND RA CONFIG...

Страница 27: ...CKET GASKET SIGHT GLASS FLANGE GASKET SECTION A A SCALE 1 16 furnace bottom oil furnace combustion chamber firebox front all 115v electrical pre assembled harnesses must be installed as per instructio...

Страница 28: ...appropriate bulk head on frame of oil burner and the flex conduit shielding secured to the bulk head by the 90 flex connector Connector should be secured from other side of bulk head by connector nut...

Страница 29: ...urnace flue blower module harness oil limit mounting bracket oil limit harness CHMF150 CHMF200 left hand ra configuration right hand ra configuration CHMF150 STEP 16 the mounting location and mounting...

Страница 30: ...impede the mechanical set point tabs and the rotary dial STEP 17 Sealing the oil flue and mounting lower heat shield Slide the flue fibre gasket over on the flue Slide the flue plate over the oil fur...

Страница 31: ...e plate ceramic fibre gasket left hand ra configuration Locate and secure lower heat shield per diagrams when configuring a CHMF150 200 furnace with the oil furnace module it is abso lutely imperative...

Страница 32: ...ve or suction lines start below the level of the oil burner For more detail on which method is more suited for a particular installation see appropriate burner manual accompanying the oil burner in th...

Страница 33: ...l addendum accom panying the blower module step 7 Remove contents of the electric furnace module kit and compare with contents list on manual addendum accompanying the electric furnace module step 8 P...

Страница 34: ...tor should also be passed through and secured by connector nut on the inside of box blower side panel blower harness lower electrical box to blower module all electrical wiring and connections must be...

Страница 35: ...ect the single pair 24V control wire not supplied to the Electric Furnace terminals on the terminal strip mounted to top of the main control box Route and secure the control wire around the back of th...

Страница 36: ...ty Switch HMFK SOLID or HMFK GLASS Door Kit steps 1 7 Follow Steps 1 to 7 from SECTION 5 4 HYBRID CHMF150 200 AS A COMBINATION WOOD ELECTRIC FURNACE steps 8 19 Follow Steps 2 to 12 from SECTION 5 3 HY...

Страница 37: ...himney draft greater than 0 06 w c 15 pa may cause an uncontrollable fire and damage the furnace venting configuration for bringing separate wood and oil furnace flues into a common vent 1 2 3 4 11 10...

Страница 38: ...CE TO COMBUSTIBLES 24 CLEARANCE TO COMBUSTIBLES SERVICE CLEARANCE RIGHT HAND RA CONFIGURATION SIDE VIEW BLOWER MODULE Drawing not to scale CLEARANCE TO COMBUSTIBLES OIL FURNACE FLUE WOOD WOOD OIL FLUE...

Страница 39: ...BOTTOM SIDES 18 457mm 6 152mm 1 25mm FOR CHMF150 ONLY Clearance can be reduced from 6 152 mm to a minimum of 3 76 mm providing that shielding with the following specifications is employed Ceiling heig...

Страница 40: ...a b366 1 m91 6 4 2 Measuring Draft Using a manometer with appropriate scale range connect testing tube between manometer and chimney connector End of testing tube should be inserted in chimney connect...

Страница 41: ...ring must be installed An ember stop of minimum 0 015 0 4 mm thick sheet steel extending 18 457 mm in front of firebox door to 2 76 mm behind the cleanout of the chimney The ember stop width must prot...

Страница 42: ...intain a minimum clearance of 12 305 mm between electric wiring carrying 120V or greater and all surfaces of the supply plenum and duct work maintain minimum 18 457 mm clearance between all furnace ex...

Страница 43: ...20V 120V 24V 24V TOGGLE SWITCH E F LINE IN FAN HIGH LOAD LINE OUT CHMF150 200 CONTROLS CIRCUITRY DIAGRAM ADD ON FIELD WIRING C HARNESS NOT USED A HARNESS NOT USED A R G B C IMPORTANT FIELD INSTALLATIO...

Страница 44: ...AMPER MOTOR WOOD THERMOSTAT 120V 120V 24V 24V TOGGLE SWITCH E F LINE IN FAN HIGH LOAD LINE OUT CHMF150 200 CONTROLS CIRCUITRY DIAGRAM WOOD ONLY FIELD WIRING C HARNESS NOT USED 2 N 3 YELLOW BLUE BLACK...

Страница 45: ...120V 120V 24V 24V TOGGLE SWITCH E F LINE IN FAN HIGH LOAD LINE OUT CHMF150 200 CONTROLS CIRCUITRY DIAGRAM WOOD ELECTRIC FIELD WIRING C HARNESS NOT USED 2 N 3 YELLOW BLUE BLACK WHITE RED MOTOR HARNESS...

Страница 46: ...Y OIL AIR DAMPER MOTOR WOOD THERMOSTAT 120V 120V 24V 24V TOGGLE SWITCH E F LINE IN FAN HIGH LOAD LINE OUT CHMF150 200 CONTROLS CIRCUITRY DIAGRAM WOOD OIL FIELD WIRING 2 N 3 YELLOW BLUE BLACK WHITE RED...

Страница 47: ...OOD LIMIT BLACK YELLOW BLACK RED WHITE ELECTRIC JUMPER 1 3 2 24 VAC 120 VAC SUPPLY OIL AIR DAMPER MOTOR WOOD THERMOSTAT 120V 120V 24V 24V TOGGLE SWITCH E F LINE IN FAN HIGH LOAD LINE OUT CHMF150 200 C...

Страница 48: ...YSTEM WOOD FURNACE 8 1 1 power outage operation high temperatures can build in the duct work to ensure air circulating in a grav ity method remove air filter from furnace ensure all supply and return...

Страница 49: ...dure in the manuals accompanying both the electric furnace and oil burner modules A summer fan switch has been added to the main electric control box This will provide low speed air circulation during...

Страница 50: ...chemicals or fluids such as gasoline engine oil OR OTHER INAPPROPRIATE MATERIALS do not operate with flue draft greater than 0 06 w c 15 pa do not store fuel or other combustible material within marke...

Страница 51: ...ed burn stack larger pieces of wood close together For long burns leave a 1 2 25 mm 51 mm bed of coals for best secondary burn performance create a channel in the ashes down to the fire bricks This ch...

Страница 52: ...the appliance Follow the directions below to minimize smoke spillage while re loading the appliance A Open the exhaust bypass damper by sliding control rod out B Open the door slightly IMPORTANT Door...

Страница 53: ...and firing techniques Check daily for creosote build up until experience shows how often cleaning is necessary Be aware that the hotter the fire the less creosote is deposited and that weekly cleaning...

Страница 54: ...h a fire extinguisher or water from a garden hose 4 Do not operate the appliance again until you are certain the chimney has not been damaged 9 0 maintenance All homes with a solid fuel burning applia...

Страница 55: ...eady for burning that fall this appliance is designed to burn natural wood only do not burn treated wood coal charcoal coloured paper cardboard solvents or garbage Higher efficiencies and lower emissi...

Страница 56: ...brackets holding the glass in place Remove all broken glass 3 Wrap the edges of the new glass with a U shaped strip of fiberglass gasket covering 1 4 6 mm on each side 4 Place the glass with the fiber...

Страница 57: ...at exchanger pipes should be inspected regularly during the burning season Easy access is provided without the use of tools simply unscrew the common knob on the exchanger access door Figure 1 Before...

Страница 58: ...and or blemishes may result normally a hot fire will clean the glass The most common reasons for dirty glass include not using sufficient fuel to get the appliance thoroughly hot using green or wet wo...

Страница 59: ...5 x4 5 x8 5 W090 0186 FIREBRICK H 1 25 x4 25 x6 W010 2410 BAFFLES I SET OF 2 W080 1092 RETAINER J W080 1093 RETAINER K W090 0200 FIREBRICK L 1 25 x4 5 x8 W090 0187 FIREBRICK M 1 25 x1 5 x6 W090 0188 F...

Страница 60: ...the home Adding more pipe or a draft inducing cap may help See the section on Selecting Wood for details Chimney height and outside conditions can negatively affect draft In these cases a small amoun...

Страница 61: ...ng periods of dampness condensation damaging chemicals or cleaners will not be the responsibility of CONTINENTAL All parts replaced under the President s Limited Lifetime warranty Policy are subject t...

Страница 62: ...W415 1112 06 12 12 62 13 0 service history 43 1...

Страница 63: ...W415 1112 06 12 12 63 44 1 14 0 NOTES...

Отзывы: