background image

7

W415-0857 / B / 02.14.11

2.3 GENERAL 

INFORMATION

When the appliance is installed at elevations above 2,000ft, and in the absence of specifi c recommendations 
from the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of 
4% for each additional 1,000ft.

No external electricity (110 volts or 24 volts) is required for the gas system operation. 

Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected. 

This appliance is equipped with a pilot light safety system referred to as an oxygen depletion sensor and is 
designed to turn off the appliance if not enough fresh air is available.

4.2C

The grounding prong must not be removed from the cord plug.

As long as the required clearance to combustibles is maintained, 
the most desirable and benefi cial location for the appliance is in the 
center of a building, thereby allowing the most effi cient use of the 
heat created. The location of windows, doors and the traffi c fl ow in 
the room where the appliance is to be located should be considered. 

If the appliance is installed directly on carpeting, vinyl tile or other 
combustible material other than wood fl ooring, the appliance shall be installed on a metal or wood panel 
extending the full width and depth. 

NOTE: This does not apply to stoves.

* Air shortage caused by an inadequate air supply, improper log positions, the addition of foreign or 
unapproved materials or the failure to properly maintain the appliance, may result in incomplete combustion of 
the fuel.  Incomplete combustion results in soot being deposited inside the fi rebox as well as surfaces outside 
the appliance.  If any soot deposits are observed, shut off the appliance immediately and arrange for it to be 
serviced by a qualifi ed technician.

We suggest that our gas 
hearth products be installed 
and serviced by professionals 
who are certified in the U.S. 
by the National Fireplace 
Institute

® (NFI) as NFI Gas 

Specialists

www.nficertified.org

2.4  RATING PLATE INFORMATION

W385-0254 / H

SERIAL NUMBER: 

    

GVF40 / CVF400

 

 

 

CERTIFIED UNDER: ANSI Z21.11.2a-2008 VOLUME II, UNVENTED ROOM HEATER

THIS APPLIANCE MAY BE INSTALLED IN AN AFTERMARKET, PERMANENTLY 
LOCATED, MANUFACTURED (MOBILE) HOME, WHERE NOT PROHIBITED BY 
LOCAL CODES. THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF 
GAS INDICATED ON THE RATING PLATE. THIS APPLIANCE IS NOT 
CONVERTIBLE FOR USE WITH OTHER GASES.

THIS IS A GAS-FIRED UNVENTED ROOM HEATER THAT REQUIRES 
ADEQUATE COMBUSTION AND VENTILATION AIR. THIS UNIT IS NOT 
APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM 
INSTALLATION.

ALTITUDE

INPUT

REDUCED INPUT

 0-2000 FT (0-610m)**

30,000 BTU/h
20,000 BTU/h

0-2000 FT (0-610m)**
28,500 BTU/h
22,000 BTU/h

MODEL

GVF40-N / CVF400-N

MODEL
GVF40-P / CVF400-P

MANIFOLD PRESSURE: 3.5” WATER COLUMN

MINIMUM SUPPLY PRESSURE: 4.5” WATER COLUMN

MAXIMUM SUPPLY PRESSURE: 7.0” WATER COLUMN

SIT CONTROL: #820637

OPERATING PILOT OXY PROTECTOR: #8214

MANIFOLD PRESSURE: 10” WATER COLUMN
MINIMUM SUPPLY PRESSURE: 11” WATER COLUMN
MAXIMUM SUPPLY PRESSURE: 13” WATER COLUMN
SIT CONTROL: #820636
OPERATING PILOT OXY PROTECTOR: #8404

** ABOVE 2,000FT, CONSULT LOCAL AUTHORITY HAVING JURISDICTION.

NOT FOR USE WITH SOLID FUEL.

WARNING: FIREPLACE SCREENS MUST BE CLOSED WHILE IN OPERATION. 

DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL 

COME IN CONTACT WITH FLAMES, OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE. DO NOT USE BLOWER INSERT, HEAT EXCHANGER INSERT OR 
OTHER ACCESSORIES NOT APPROVED FOR USE WITH THIS HEATER. IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTAINANCE CAN CAUSE PROPERTY 
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. REFER TO THE OWNER’S INFORMATION MANUAL PROVIDED WITH THIS APPLIANCE. INSTALLATION AND SERVICE MUST BE 
PERFORMED BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.

MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS:
TOP / SIDES / BACK / FLOOR 

0”

RECESSED DEPTH 

 

25

¼"

MANTLE 

 

  5”*

* MAXIMUM HORIZONTAL EXTENSION: 2”.
SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS.

ELECTRICAL RATING: 115V, 0.82AMP, 60HZ
OPTIONAL FAN KIT: GZ550-KT

WOLF STEEL LTD.  

24 NAPOLEON ROAD. BARRIE, ONTARIO L4M 0G8 CANADA

XXXXXX

For rating plate 
location, see 
“INSTALLATION 
OVERVIEW” section.

This illustration is for 
reference only.  Refer 
to the rating plate 
on the appliance for 
accurate information.

FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!  

APPLIANCE

NG

LP

Altitude (FT)

0-2,000

0-2,000

Max. Input (BTU/HR)

30,000

30,000

Min. Inlet Gas Supply Pressure

4.5" Water Column

11" Water Column

Max. Inlet Gas Supply Pressure

7" Water Column

13" Water Column

Manifold Pressure (Under Flow Conditions)

3.5" Water Column

10" Water Column

SAMPLE

PL

PL

ER

ER

ED UNVENT

ED UNVE

MBUSTION AND V

MBUSTION AND

FOR BEDROOM, BATHR

OR BEDROOM, BAT

ION.

ON.

D INPUT

 INPUT

0-2000 FT (0-610m)*

0-2000 FT (0-610m)*

28,500 BTU/h

500 BTU/h

22,000 BTU/h

0 BTU/h

MODEL
GVF40-P / CVF400-

GVF40-P / CVF40

MANIFO
MINIM
MA
S

FT, CONSULT LOCAL AUTHORITY 

FT, CONSULT LOCAL AUTHORITY

OT FOR USE WITH S

FOR USE WITH S

BE CLOSED WHILE IN O

BE CLOSED WHILE IN 

PPLIED BY THE MANUFACTURER

PPLIED BY THE MANUFACTUR

THIS HEATER. IMPROPER INSTAL

HIS HEATER. IMPROPER INSTA

ER TO THE OWNER’S INFORMATI

O THE OWNER’S INFORMAT

E AGENCY OR THE GAS SUPPLIE

CY OR THE GAS SUPPLIE

IBLE MATERIALS:

BLE MATERIALS:

0”

0”

25

25

¼

¼

"

"

5”*

M 0G8 CAN

M 0G8 CAN

SAMPLE

Содержание CVF40N

Страница 1: ...lding Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be...

Страница 2: ...END INSTALLATION 15 5 1 FRAMING 15 5 2 BRICK PANEL INSTALLATION 16 5 3 FACING 16 5 4 FINISHING 16 6 0 SEE THRU INSTALLATION 17 6 1 FRAMING 17 6 2 BRICK PANEL INSTALLATION 18 6 3 FACING 18 6 4 FINISHIN...

Страница 3: ...VIEW Louvres see LOUVRE INSTALLATION section Hood see HOOD section Counter top see COUNTER TOP BAR INSTALLATION section Logs see LOG PLACEMENT section Bricks see BRICK PANEL INSTALLATION section Ratin...

Страница 4: ...o protect children from hot surfaces These screens and guards must be fastened to the floor Any safety screen or guard removed for servicing must be replaced prior to operating the appliance It is imp...

Страница 5: ...2 GAS ELECTRICAL INLET 41 4 61 2 321 2 38 4 SIDED SEE THRU 36 401 2 271 2 221 8 221 8 21 2 GAS ELECTRICAL INLET 41 4 61 2 321 2 38 38 251 8 36 401 2 27 221 8 221 8 21 2 GAS ELECTRICAL INLET 41 4 61 2...

Страница 6: ...pressures in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply pi...

Страница 7: ...AND BED SITTING ROOM INSTALLATION ALTITUDE INPUT REDUCED INPUT 0 2000 FT 0 610m 30 000 BTU h 20 000 BTU h 0 2000 FT 0 610m 28 500 BTU h 22 000 BTU h MODEL GVF40 N CVF400 N MODEL GVF40 P CVF400 P MANI...

Страница 8: ...owever if a problem should occur A Ensure sufficient combustion and circulation air B Use a dehumidifier C Do not use the unvented room appliance as a primary heat source WARNING IF THE AREA IN WHICH...

Страница 9: ...el burning appliances within this space then the 30 000 BTU h input of the appliance is suitable to be installed This also assumes that the construction of this space is not unusually tight 19 3 EXAMP...

Страница 10: ...provide sufficient movement for shifting the burner assembly on it s side to aid with servicing components F Check for gas leaks by brushing on a soap and water solution WARNING RISK OF FIRE EXPLOSION...

Страница 11: ...itch and replace with the leads from the wall switch millivolt thermostat 50 1 3 1 2 WARNING DO NOT CONNECT EITHER THE WALL SWITCH THERMOSTAT OR GAS VALVE DIRECTLY TO 110 VOLT ELECTRICITY 3 5 MOBILE H...

Страница 12: ...AIR SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE PREVENT CONTACT WITH SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS BLOCK OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN I...

Страница 13: ...irectly on of the top extension NOTE Maximum weight tolerance is 400 lbs provided that it is evenly distributed across the top extensions of the appliance In order to achieve a counter top or bar type...

Страница 14: ...ion with this appliance system When roughing in the appliance raise the appliance to accommodate for the thickness of the finished floor materials i e Tile carpeting hard wood which if not planned for...

Страница 15: ...USE OVER HEATING AND FIRE PREVENT CONTACT WITH SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS BLOCK OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN IN INSULATION MAKE SURE INS...

Страница 16: ...ustible material brick stone or ceramic tile may protrude in these areas It is not necessary to install a hearth extension with this appliance system When roughing in the appliance raise the appliance...

Страница 17: ...TION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS BLOCK OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN IN INSULATION MAKE SURE INSU LATION AND OTHER MATERIALS ARE SECURED WHEN CONSTRUCTING THE ENCLOSU...

Страница 18: ...ombustible material brick stone or ceramic tile may protrude in these areas It is not necessary to install a hearth extension with this appliance system When roughing in the appliance raise the applia...

Страница 19: ...ACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE PREVENT CONTACT WITH SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS BLOCK OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN IN INSU...

Страница 20: ...not necessary to install a hearth extension with this appliance system When roughing in the appliance raise the appliance to accommodate for the thickness of the finished floor materials i e Tile car...

Страница 21: ...TC ARE CLEARLY MAINTAINED WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL THE PAINT OR LACQUER MUST BE HEAT RESISTANT TO PREVENT DISCOLOURATION 73 1 WARNING LOGS MUST BE PLACED IN THEIR EXACT LOCATIO...

Страница 22: ...should rest in the groove on top of log 2 The slot in the underside of piece 3b fits over 3a Place the end of piece 3b onto the pin F As with log 1 log 4 is also cradled by the texture of the burner...

Страница 23: ...he base 5a slopes outwards between logs 2 and 4 As with pieces 3a b piece 5b fits over piece 5a Place the end of piece 5b onto the pin H The upper end of log 5 rests in the groove on top of log 4 and...

Страница 24: ...SHIELD STAND OFF REMOVAL Remove the backing of the logo supplied and place on the screen cover as indi cated 8 7 LOGO PLACEMENT A B C SLOT A B C CLIPS CENTRE SLOT TAB SLOT HINGE CLIP 57 2 UPPER LOUVR...

Страница 25: ...tall the thermal switch into the appliance bracket Then replace the bracket in the location it was removed Connect the two ends of the unattached wires by the bracket to the thermal switch Connect the...

Страница 26: ...electric power to the appliance Open the control door Turn the gas knob clockwise to off Wait five 5 minutes to clear out any gas If you smell gas including near the floor STOP Follow B in the above s...

Страница 27: ...UTTER IS IMPROPERLY ADJUSTED WARNING 49 5 This appliance has an air shutter that has been factory set open according to the chart below Regardless of venturi orientation closing the air shutter will c...

Страница 28: ...Verify proper operation after servicing This appliance and its venting system should be inspected before use and at least annually by a qualified service person The appliance area must be kept clear a...

Страница 29: ...T OF WIRE 3 W385 0430 CONTINENTAL LOGO 4 GL 657 BGD40 LOG SET 5 W135 0284 LOG 1 6 W135 0285 LOG 2 7 W135 0286 LOG 3 PIECE A 8 W135 0287 LOG 3 PIECE B 9 W135 0288 LOG 4 10 W135 0289 LOG 5 PIECE A 11 W1...

Страница 30: ...N 35 W010 2146 PAN BURNER 36 W475 0624 FIBRE BURNER COVER 37 W662 0001 NATURAL GAS OXYGEN DEPLETION SENSOR SYSTEM 37 W662 0005 PROPANE GAS OXYGEN DEPLETION SENSOR SYSTEM 38 W660 0005 BURNER ON OFF SWI...

Страница 31: ...31 W415 0857 B 02 14 11 7 23 25 24 36 32 22 31 28 34 8 9 6 10 11 5 16 21 18 17 20 27 33 30 41 42 4 37 14 12 15 13 25 35 43...

Страница 32: ...low Service or replace Oxygen Depletion Sensor System Correct piping and or regulator to provide correct pressure Ensure adequate supply pressure Pilot goes out when the gas knob is released The gas v...

Страница 33: ...Depletion Sensor System Call the gas distributor Pilot goes out while standing Main burner is in OFF position Gas piping is undersized Turn on all gas appliances and see if pilot flame flutters dimin...

Страница 34: ...of the methods described in ANSI Z223 1 NFPA 54 or the applicable local code Not enough ventilation air Increase fresh air supply Use one of the methods described in ANSI Z223 1 NFPA 54 or the applica...

Страница 35: ...s due to water weather damage long periods of dampness condensation damaging chemicals or cleaners will not be the responsibility of NAPOLEON All parts replaced under the President s Limited Lifetime...

Страница 36: ...36 W415 0857 B 02 14 11 16 0 SERVICE HISTORY 43 1...

Отзывы: