18
W415-0858 / A / 02.14.11
This appliance has an air shutter that
has been factory set open according
to the chart below:
Closing the air shutter will cause a
more yellow fl ame, but can lead to carboning. Opening
the air shutter will cause a more blue fl ame, but can cause
fl ame lifting from the burner ports. The fl ame may not ap-
pear yellow immediately; allow 15 to 30 minutes for the fi nal fl ame color to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED INSTALLER!
Access plate and gasket must be re-installed after adjustment.
The alternate access is to remove the glass media, media tray and burner from the appliance and then adjust the
air shutter.
NOTE: When removing the media tray make sure the glass media are away from the center of
the screen, exposing the burner, before lifting media tray out.
When replacing burner, absolutely no glass can be in cup surrounding the orifi ce.
HINT:
If glass falls into cup and
surrounds the orifi ce, insert a clean bag into a vacuum cleaner and vacuum out glass media. Replacement glass
media can be ordered from Wolf Steel Ltd.
9.0 ADJUSTMENTS
9.1 PILOT BURNER ADJUSTMENT
9.2 VENTURI
ADJUSTMENT
Adjust the pilot screw to provide properly sized fl ame. Turn in a
clockwise direction to reduce the gas fl ow.
Check Pressure Readings:
Inlet pressure can be checked by turning screw (A) counter-
clockwise 2 or 3 turns and then placing pressure gauge tubing over
the test point. Gauge should read 7” (minimum 4.5”) water column
for natural gas or 13” (11” minimum) water column for propane.
Check that main burner is operating on “HI”.
Outlet pressure can be checked the same as above using screw (B). Gauge should read 3.5” water column for
natural gas or 10” water column for propane. Check that main burner is operating on “HI”.
AFTER TAKING PRESSURE READINGS, BE SURE TO TURN SCREWS CLOCKWISE FIRMLY TO
RESEAL. DO NOT OVERTORQUE.
Leak test with a soap and water solution.
39.1
A
B
PILOT SCREW
AIR SHUTTER
ACCESS PLATE
THE FRONT OF THE APPLIANCE BECOMES VERY HOT DURING OPERATION. LET THE APPLIANCE
COOL COMPLETELY BEFORE CONDUCTING SERVICE.
!
WARNING
NG
LP
CDI-30G
0
1/4"