Minimum clearance to combustible construction from appliance and vent surfaces:
Sides, back, bottom and top of the unit
0"
Recessed depth
22"
All around the vent pipe*
2"
Enclosure top
45 1/2"
Ceiling
54" from bottom of unit
*HORIZONTAL VENT SECTIONS:
A minimum clearance of 2" all around the vent pipe on all horizontal runs to
combustibles is required. Use
fi
restop spacer W010-2116 (supplied).
*VERTICAL VENT SECTIONS:
A minimum of 1" all around the vent pipe on all vertical runs to combustibles is
required except for clearances in appliance enclosures. Use
fi
restop spacer W500-0367 (not supplied).
It is best to frame your appliance after it is positioned and the vent system is installed. Use 2x4's and frame to local
building codes. It is not necessary to install a hearth extension with this appliance system.
When roughing in the appliance, raise the appliance to accommodate for the thickness of the
fi
nished
fl
oor materials,
i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower access door and the
installation of many decorative
fl
ashing accessories.
Combustible materials may be installed
fl
ush with the front of the appliance but must not cover or protrude past any
of the black face-areas of the appliance. Non-combustible material (brick, stone or ceramic tile) may protrude in these
areas.
5.1 MINIMUM CLEARANCE TO COMBUSTIBLES