7
W415-0803 / C / 04.19.12
3.1 RATING PLATE INFORMATION
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to
the model, venting and gas type of the appliance.
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
W385-0342 / H
CERTIFIED UNDER / HOMOLOGUE SELON LES NORMES: CSA 2.22b-2009, ANSI Z21.50b-2009 VENTED GAS FIREPLACE / FOYER AU GAZ AVEC EVACUATION.
FOYER A GAZ VENTILE DIRECT. HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER, UNE
SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE SI SON
INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE MAISONS
MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS DE LA NORME DE
SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES, TITRE 24 CFR, SECTION 3280.
DANS LE CAS OU CETTE NORME D'ETATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERER A LA NORME
RELATIVE AU CRITERE DE MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS
DANS LES MAISONS MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A. LORSQU'IL
EST INSTALLE AVEC LA TROUSSE POUR ECRAN GD-565KT, LE FOYER EST CONFORME A LA NORME DE
CERTIFICATION DE L'ACG CR95-006.
DIRECT VENT GAS FIREPLACE. SUITABLE FOR BEDROOM, BATHROOM AND BED-SITTING ROOM
INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE
WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES,
IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONTRUCTION AND
SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT
APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED
HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A. WHEN INSTALLED
WITH SCREEN KIT GD-565KT, THE FIREPLACE COMPLIES WITH CGA CERTIFICATION
REQUIREMENT CR95-006.
9700539 (WSL)
4001657 (NGZ)
4001658
(NAC)
4001659
(WUSA)
BGD36CFNTR
BCDV36CFNTR MODEL BGD36CFPTR
BCDV36CFPTR
0-4500FT (0-1370m)
ALTITUDE / ELEVATION
0-4500FT (0-1370m)
17,000 BTU/h
INPUT / ALIMENTATION
17,000 BTU/h
12,000 BTU/h
REDUCED INPUT / ALIMENTATION REDUITE
12,000 BTU/h
MANIFOLD PRESSURE:
3.5" WATER COLUMN
MANIFOLD PRESSURE:
10" WATER COLUMN
PRESSION AU COLLECTEUR:
3.5" D'UNE COLONNE D'EAU
PRESSION AU COLLECTEUR:
10" D'UNE COLONNE D'EAU
MINIMUM SUPPLY PRESSURE:
4.5" WATER COLUMN
MINIMUM SUPPLY PRESSURE:
11" WATER COLUMN
PRESSION D'ALIMENTATION MINIMALE:
4.5" D'UNE COLONNE D'EAU
PRESSION D'ALIMENTATION MINIMALE:
11" D'UNE COLONNE D'EAU
MAXIMUM SUPPLY PRESSURE:
7.0" WATER COLUMN
MAXIMUM SUPPLY PRESSURE:
13" WATER COLUMN
PRESSION D'ALIMENTATION MAXIMALE:
7.0" D'UNE COLONNE D'EAU
PRESSION D'ALIMENTATION MAXIMALE:
13" D'UNE COLONNE D'EAU
NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS
DOORS CERTIFIED WITH THIS UNIT ONLY.
WARNING:
THIS FIREPLACE USES AND REQUIRES A FAST ACTING THERMOCOUPLE. REPLACE
ONLY WITH A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD.
DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES,
OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS /
DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES:
TOP/ DESSUS
0
RECESSED DEPTH / PROFONDEUR D'ENCASTRE
17.25"
FLOOR / PLANCHER
0
VENT SIDES / COTES DE L'EVENT
1"
SIDES / COTES
0
VENT TOP / EVENT SUPERIEUR
2"
BACK / ARRIERE
0
VENT BOTTOM / EVENT INFERIEUR
1"
MANTEL / MANTEAU
12" *
* MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION HORIZONTALE MAXIMALE: 2". SEE INSTRUCTION
MANUAL FOR GREATER EXTENSIONS. REFERER AU MANUEL D'INSTRUCTION POUR DES
EXTENSIONS PLUS GRANDES.
SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS.
REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR LES LONGUEURS
D'EVACUATION MINIMALE ET MAXIMALE.
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC
CET APPAREIL. UTILISER AVEC LES PORTES VITREES
HOMOLOGUEES SEULEMENT AVEC CETTE UNITE.
AVERTISSEMENT:
CE FOYER UTILISE ET REQUIERT UN THERMOCOUPLE À ACTION RAPIDE.
REMPLACEZ UNIQUEMENT AVEC UN THERMOCOUPLE À ACTION RAPIDE DE WOLF STEEL LTÉE.
N’AJOUTEZ PAS A CET APPAREIL AUCUN MATERIAU DEVANT ENTRER EN CONTACT AVEC LES FLAMMES
AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS
INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS
NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM.
L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'EVACUATION PROPRE A NAPOLEON.
REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR L'EVACUATION PRECISE. IL EST
IMPORTANT DE BIEN REINSTALLER ET RESCELLER L'EVENT APRES AVOIR ASSURE LE MAINTIEN DU
SYSTEME DE PRISE D'AIR.
ELECTRICAL RATING / CLASSIFICATION: 115V 0.82AMP, 60HZ
OPTIONAL FAN KIT / ENSEMBLE DE VENTILATEUR FACULTATIF: GZ550-KT, GD65
SERIAL NUMBER/NO. DE SERIE:
BGD36CF
SAMPLE
ance fo
ance
SAMPLE
/ FOYER AU GAZ AVEC EVACUAT
FOYER AU GAZ AVEC EVACUAT
OMOLOGUE POUR INSTALLATION DANS U
OLOGUE POUR INSTALLATION DANS U
TUDIO. APPROPRIE POUR INSTALLATION DAN
APPROPRIE POUR INSTALLATION DAN
ORME AUX EXIGENCES DE LA NORME CAN/C
XIGENCES DE LA NORME CAN/C
S AU GAZ, EN VIGUEUR AU CANADA OU A
GUEUR AU CANADA OU A
E CONSTRUCTION DE MAISONS MANUFACTU
MAISONS MANUFACT
OU CETTE NORME D'ETATS-UNIS NE PEUT ET
OU CETTE NORME D'ETATS-UNIS NE PEUT ET
AU CRITERE DE MESURES DE SECURITE CON
U CRITERE DE MESURES DE SECURITE CO
ES MAISONS MANUFACTURES, LES SITES ET LE
MAISONS MANUFACTURES, LES SITES ET L
NSTALLE AVEC LA TROUSSE POUR ECRAN GD-
LE AVEC LA TROUSSE POUR ECRAN G
4001657 (NGZ)
4001657 (NGZ)
4001659 (WUSA)
4001659 (WUSA)
PP
L
L
BGD36CFPTR
BGD36CFPTR
LEVATION
LEVATION
0-4500FT (0-1370m
0-4500FT (0-1370m
IMENTATION
MENTATION
17,000 BTU/h
/ ALIMENTATION REDUITE
12,000 BTU/h
MENTATION REDUITE
PL
UMN
MN
MANIFOLD PRESSURE:
ANIFOLD PRES
10" WAT
D'EAU
D'EAU
PRESSION AU COLLECTEUR:
ESSION AU CO
COLUMN
COLUMN
MINIMUM SUPPLY PRESSU
MINIMUM SUPPLY PR
NNE D'EAU
E D'EAU
PRESSION D'ALIMENTAT
PRESSION D'ALIMENTA
ATER COLUMN
OLUMN
MAXIMUM SUPPLY PR
MAXIMUM SUPPLY PR
COLONNE D'EAU
OLONNE D'EAU
PRESSION D'ALIME
PRESSION D'ALIME
GLASS
GLASS
HERMOCOUPLE. REPLACE
OUPLE. REPLACE
L LTD.
N CONTACT WITH THE FLAMES,
N CONTACT WITH THE FLAMES
APPLIANCE.
APPLIANC
ONDEUR D'ENCASTRE
17.25"
EUR D'ENCASTRE
17.25"
L'EVENT
T
1"
1"
PERIEUR
2"
2"
NT INFERIEUR
1"
1"
SION HORIZONTALE MAXIMALE: 2". SEE INS
SION HORIZONTALE MAXIMALE: 2". S
RER AU MANUEL D'INSTRUCTION POUR DES
RER AU MANUEL D'INSTRUCTION PO
MANUAL FOR MINIMUM AND MAXIMUM VEN
MANUAL FOR MINIMUM AND MAXIMUM VE
STALLATION DE PROPRIETAIRE POUR LES
ALLATION DE PROPRIETAIRE POUR LES
E ET MAXIMALE.
MAXIMALE.
ON, L4M 0G8 CANADA
ON, L4M 0G8 CANADA
UN COMBU
UN COM
CET APP
CET APP
HOMO
HOMO
AVE
AVE
R
RE
E
3.0 VENTING
7.1A
THIS APPLIANCE USES A 4” EXHAUST / 7” AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create dif
fi
culty in burner start-up and/or carboning. Under extreme vent
con
fi
gurations, allow several minutes (5-15) for the
fl
ame to stabilize after ignition. Provide a means for
visually checking the vent connection to the appliance after the appliance is installed. Use a
fi
restop, vent pipe
shield or attic insulation shield when penetrating interior walls,
fl
oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
!
WARNING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3 FEET
FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.