32
W415-0803 / C / 04.19.12
* HORIZONTAL VENT SECTIONS
- A minimum clearance of 1" at the bottom and sides and 2" at the top of
the vent pipe on all horizontal runs to combustibles is required. Use
fi
restop spacer W010-1777 (supplied).
* VERTICAL VENT SECTIONS
- A minimum of 1" all around the vent pipe on all vertical runs to combustibles
is required except for clearances in appliance enclosures. See "MINIMUM ENCLOSURE CLEARANCES" sec-
tion. Use
fi
restop spacer W500-0096 (not supplied).
Minimum clearance to combustible construction from appliance and vent surfaces:
Non-combustible
Framing:
Top
- 0" to stand-offs if using optional clean face surround.
Combustible Framing:
Sides, back and bottom of appliance
- 0" to rear.
Top
- 3 1/2" to stand-offs if using optional clean face surround.
Combustible
Finishing:
Sides, bottom and top
- 0" to appliance edge.
Enclosure top
- 13 1/2" to top of appliance.
Recessed
depth -
25"
Top, sides and bottom of vent pipe*
- 2"
Ceiling
-
54"
from
bottom
of
appliance.
6.1 INSTALLING
STAND-OFFS
These appliances are supplied with two standoffs. For conve-
nience, the standoffs have been shipped
fl
at and located on the
top at the front. Before framing ensure the standoffs are bent up
and screwed into place ensuring a height of 4.5".
NOTE: The information and dimensions in this section repre-
sent the minimum clearances to combustible material.
It is best to frame your appliance after it is positioned and the vent
system is installed. Use 2x4's and frame to local building codes.
A steel header is required if using optional clean face surround.