Example Connection to a Device 

 

 

 

 

 

 

Baud Rate 

See the table below for the baud rate that can be set with the product. 
Error rate differs depending on the set baud rate. 

Baud Rate (bps) 

Error (%) 

300 

0.00 

600 

0.00 

900 

0.00 

1,200 

0.00 

2,400 

0.00 

4,800 

0.00 

9,600 

0.16 

14,400 

0.16 

19,200 

0.16 

28,800 

0.16 

38,400 

0.16 

57,600 

0.16 

115,200 

0.16 

 

 

External device

TxD
RxD
RTS
CTS
DTR
DSR
SG

TxD
RxD
RTS
CTS
DTR
DSR
SG

Содержание CONPROSYS CPS-PC341MB-ADSC1-9201

Страница 1: ... CONTENTS CODESYS Modbus Master CPS PC341MB ADSC1 9201 Introduction 4 Safety Precautions 12 Product Nomenclature and Function 21 Setup 36 Installation 43 Appendix 67 Optional Products 78 Customer Support and Inquiry 80 Index 82 ...

Страница 2: ...nd the storage in EU signatory 20 Product Nomenclature and Function 21 1 Nomenclature of Product Components 22 2 Description of Product Components 23 1 Power Connector 23 2 Debug Connector 23 3 SD Card Slot 23 4 USB Port 24 5 RS 232C Serial Port 25 6 LED Indicator 26 7 Resets switch 26 8 Shutdown switch 27 9 DIP switch 27 10 LAN Port 28 11 Digital Input Counter Input Digital Output Connecter 30 12...

Страница 3: ... 52 3 RS 422A 485 53 4 RS 232C 58 5 Analog Input 60 6 Digital Input Counter Input 62 7 Digital Output 64 Appendix 67 1 Specifications 68 1 Specifications 68 2 Power Requirements 72 2 Physical Dimensions 73 3 The Details of Model Name 74 4 Battery Disposal 75 1 Battery Specification 75 2 How to remove the battery 75 5 Connector Check 76 Optional Products 78 1 Optional Products 79 Customer Support a...

Страница 4: ... 4 Introduction This section provides necessary information of the product such as the outline bundled items and manuals before actual use ...

Страница 5: ... WEB Setting Download from the Contec website PDF Read the Followings as Necessary Name Purpose Contents How to get CONPROSYS Cloud Data Service 2 CDS2 Manual Read this to understand the outline of the CONPROSYS Cloud Data Service 2 This describes the outline and specification of the CONPROSYS Cloud Data Service 2 as well as how to operate the product Download from the Contec website PDF CONPROSYS...

Страница 6: ...g the product visit our website to check the firmware version and update to the latest one if necessary Updating firmware to the latest version will resolve troubles and stabilize the operation Download https www contec com download Refer to the Reference Manual Software for the details of the firmware updating ...

Страница 7: ...nter channel isolated analog input RS232C and LAN interface This product contains the CODESYS Soft PLC You can create your own PLC program and run with the CODESYS software CODESYS is a device independent PLC programming system that is complied with the IEC 61131 3 standard and supports all standard programming languages such as ST or LD CODESYS is a registered trademark of 3S Smart Software Solut...

Страница 8: ...g interfaces With the CONPROSYS series data collected from various types of facilities can be managed centrally LAN SD Card Slot USB Digital Input Digital Output Analog Input Current Analog Output Current Counter RS 422A 485 RS 232C 3GSIM Standard SIM CAN Analog Input Voltage Analog Output Voltage Interface within Non interface within ...

Страница 9: ...olated analog input It supports differential input and is capable of precise measurement of voltage with potential differences Adaptable to a temperature range between 20 and 60 C The product is capable of operating in the temperature between 20 and 60 C It can be installed in the various environments Compact design Compact design 188 0 W x 78 0 D x 30 5 H features flexibility in installation A po...

Страница 10: ...ct can be replaced in a short length of time Equipped with LED for an operation check The product has LED for an operation check which helps you visually confirm the communication status of each interface Choice of a battery with a longer life With a choice of a long life battery the Contec is creating longer lasting products 2 Software Features Feature the CODESYS SoftPLC CODESYS is a device inde...

Страница 11: ...Power Analog 5 pin Connector 1 RS 422A 485 10 pin Connector 1 Digital CODESYS Runtime license 1 attached on the bottom face of the product This product is verified in conformity with our recommended power supply In case you use other power supplies thus it may not be able to fulfil certification requirements Please see the Contec website regarding power supply recommendation https www contec com T...

Страница 12: ... 12 Safety Precautions Understand the following definitions and precautions to use the product safely Never fail to read them before using the product ...

Страница 13: ...moderate injury or in property damage Informations de sécurité Ce document contient des informations relatives à la sécurité sous utilisation des symboles suivant afin d éviter tout accident risquant d entraîner des blessures ou la mort et la destruction de l équipement et des ressources Veillez à comprendre les significations de ces mots signalétiques pour utiliser l équipement en toute sécurité ...

Страница 14: ...uclear power medical equipment or other applications that require a very high level of reliability Do not use the product in such applications If using the product in applications where safety is critical such as in railways automotive or disaster prevention or security systems please contact your retailer CAUTION Be certain the following requirements are satisfied when using the product Indoor us...

Страница 15: ...the event of failure or abnormality foul smells or excessive heat generation unplug the power cables immediately and contact your retailer To connect with peripherals use a grounded shielded cable To clean the product wipe it gently with a soft cloth dampened with either water or mild detergent Do not use chemicals or a volatile solvent such as benzene or thinner to prevent the paint to be scraped...

Страница 16: ... un incendie ou un choc électrique Ne pas installer le produit à un endroit instable ou sans un montage complet Faute de quoi le dispositif risque de tomber S assurer de raccorder le produit à la tension d alimentation électrique indiquée Une tension différente peut provoquer un incendie ou un choc électrique Veuillez utiliser le produit selon les spécifications du fabricants sinon la protection o...

Страница 17: ...t spécifiées température humidité vibration et impact Le produit doit toujours être mis à la terre Éviter d installer le produit dans des endroits où la ventilation du produit pourrait être compromise Une aération insuffisante peut faire chauffer le produit et risque de l endommager ou d entraîner une défaillance Ne pas utiliser le produit à proximité de dispositifs qui génèrent une intense force ...

Страница 18: ...au local RS 232C RS 422A 485 AI DIO module d entrée sortie numérique mise à la terre etc Consulter un spécialiste pour la sélection l achat et l installation d un dispositif contre les surtensions Respecter les procédures d élimination précisées dans les lois et les ordonnances municipales pertinentes lors de l élimination du produit Alimentation électrique du produit et E S numérique Pour une cer...

Страница 19: ... used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense FCC WARNING Changes or modifications not expressly approved by the party responsible for compliance could void the users...

Страница 20: ...r accumulators at their end of life should be disposed separately from the household waste If a chemical symbol is printed beneath the symbol mark shown above it indicates that the battery or accumulator contains a heavy metal at a certain concentration The concentration standard is indicated below Hg mercury 0 0005 Cd cadmium 0 002 Pb lead 0 004 These ingredients may cause hazardous conditions fo...

Страница 21: ... 21 Product Nomenclature and Function This section describes product component names and their functions pin assignment of each connector ...

Страница 22: ...7 Reset Switch This resets the product 8 Shutdown Switch This shuts down the product 9 DIP Switch This is used for system setup and RS 422A 485 setup 10 LAN Port This is a connector for LAN 11 Digital Input Counter Input Digital Output Connector This is a connector for digital input counter input digital output Use the 10 pin connector included in the package 12 Analog Input Connector This is a co...

Страница 23: ...e to connect to external power Connector type DEGSON 15EDGK 3 5 03P 14 1000AH or equivalent The type of connectors in the package differs depending on the period of manufacturing To check the supplied connector type refer to Appendix Connector Check Pin Assignment Pin No Signal Name 1 FG 2 V GND 3 V 12 24VDC 2 Debug Connector Do not use this 3 SD Card Slot Insert the SD card to store such as data ...

Страница 24: ... of USB interface of TYPE A Pin Assignment Pin No Signal Name 1 USB_VCC 2 DATA 3 DATA 4 USB_GND CAUTION If you use the USB device with bus power the ambient temperature should be 55 C or lower ATTENTION Si vous utilisez le dispositif USB avec alimentation par bus la température ambiante devrait être de 55 C ou moins 4 1 ...

Страница 25: ...e baud rate is 115 200bp Max Pin Assignment Pin No Signal Name Direction Description 1 CD Input Carrier detection 2 RD Input Reception data 3 TD Output Transmission data 4 DTR Output Data terminal ready 5 GND Signal ground 6 DSR Input Data set ready 7 RTS Output Request to send 8 CTS Input Clear to send 9 RI Input Ring Indicate 1 5 6 9 9 pin D SUB Male No 4 40UNC inch nut ...

Страница 26: ...A 485 OFF It indicates there is no data transmission by RS 422A 485 RX COM A Yellow Flashing It flashes upon receiving data by the RS 422A 485 OFF It indicates there is no data reception by RS 422A 485 TX COM B Yellow Flashing It flashes upon transmitting data by the RS 232C OFF It indicates there is no data transmission by the RS 232C RX COM B Yellow Flashing It flashes upon transmitting data by ...

Страница 27: ...he RX Terminator OFF Disable the RX Terminator 3 ON Internal connection state of TX and RX Short Half Duplex OFF Internal connection state of TX and RX Open Full Duplex 4 ON Internal connection state of TX and RX Short Half Duplex OFF Internal connection state of TX and RX Open Full Duplex SW1 1 ON RTS Communication Mode Half Duplex OFF RTS Communication Mode Full Duplex 2 System Reservation Alway...

Страница 28: ...C This pin is left unconnected 5 N C This pin is left unconnected 6 RX Reception data input 7 N C This pin is left unconnected 8 N C This pin is left unconnected Color and Description LED Color Display Description Speed Orange ON It indicates that LAN port is connected at 100Mbps OFF It indicates that LAN port is connected at 10Mbps or not connected Link Act Green ON It indicate that LAN port is a...

Страница 29: ... a large amount of data or high speed response is requested an external switching HUB will be required ATTENTION Le mode avec concentrateur de commutation du produit peut être plus lent que d autres concentrateurs de commutation normaux En présence d un volume élevé de données ou lorsqu une réponse haute vitesse s avère nécessaire il faudra un concentrateur de commutation externe ...

Страница 30: ... 3 DI1 This indicates the input signals of channel 1 It connects the output signals from the other devices 4 DI2 CNT0 This indicates digital input signals of channel 2 and counter signals of channel 0 It connects the output signals from the other devices 5 DI3 CNT1 This indicates digital input signals of channel 3 and counter signals of channel 1 It connects the output signals from the other devic...

Страница 31: ... connector included in the package to connect to external power Connector type DEGSON 15EDGK 3 5 03P 14 1000AH or equivalent The type of connectors in the package differs depending on the period of manufacturing To check the supplied connector type refer to Appendix Connector Check Pin Assignment No Signal Name Description 1 AI Analog input signals 2 AI Analog input signals 3 AGND Analog ground 1 ...

Страница 32: ...ackage to connect to external power Connector type DEGSON 15EDGK 3 5 05P 14 1000AH or equivalent The type of connectors in the package differs depending on the period of manufacturing To check the supplied connector type refer to Appendix Connector Check Pin Assignment No Signal Name Description 1 TX Transmission data 2 TX Transmission data 3 RX Receptions data 4 RX Receptions data 5 SG Signal gro...

Страница 33: ...recognition of input signals from being affected by noise or chattering Operation Principle The digital filter checks the input signal level during the sampling time of 1 4 cycles of digital filter setting time When the signal level remains the same over the digital filter setting time sampling four times the digital filter recognizes that signals as normal and changes the filter output signal lev...

Страница 34: ...6 06h 8μsec 17 11h 16 384msec 7 07h 16μsec 18 12h 32 768msec 8 08h 32μsec 19 13h 65 536msec 9 09h 64μsec 20 14h 131 072msec 10 0Ah 128μsec The following lists the relation between digital filter time and setting data Digital Filter Time sec 2n 8x106 n Setting Data 0 20 CAUTION The digital filter applies to all input channels it cannot apply to only specific input pins To pass input signal without ...

Страница 35: ... il ne peut pas se limiter uniquement à des broches d entrée spécifiques Pour transmettre correctement un signal d entrée la largeur de l impulsion doit être le double du délai réglé pour le filtre Un filtre numérique ne fonctionne pas de manière efficace si le filtre numérique est données de réglage 1 à 10 inférieur au temps de réponse du photocoupleur ...

Страница 36: ... 36 Setup This section describes how to set switches and an antenna that are necessary to operate the product ...

Страница 37: ...setup Set the terminators on or off in accordance with the device which you are communicating with The DIP switch SW2 sets the terminator The terminators on the product are 100Ω resistors If you intend to use a terminator of other than 100Ω set the terminator switch OFF first and insert an external terminator A or D B or C Use the terminator inside Set the terminator outside When using the termina...

Страница 38: ...of TX and RX Short Half Duplex OFF Internal connection state of TX and RX Open Full Duplex 4 ON Internal connection state of TX and RX Short Half Duplex OFF Internal connection state of TX and RX Open Full Duplex SW1 1 ON RTS Communication Mode Half Duplex OFF RTS Communication Mode Full Duplex 2 System Reservation Always OFF 3 System Reservation Always OFF 4 System Reservation Always OFF 5 System...

Страница 39: ...th The DIP switch SW2 sets the terminator The terminators on the product are 100Ω resistors If you intend to use a terminator of other than 100Ω set the terminator switch OFF first and insert an external terminator Use the terminator inside Set the terminator outside C O M B USB R S 232 C 1 ON 2 3 4 1 2 3 4 5 6 SW2 SW1 Terminator Bit 1 Terminator Bit 2 Terminator Bit 2 Terminator Bit 1 RxD TxD TxD...

Страница 40: ...of TX and RX Short Half Duplex OFF Internal connection state of TX and RX Open Full Duplex 4 ON Internal connection state of TX and RX Short Half Duplex OFF Internal connection state of TX and RX Open Full Duplex SW1 1 ON RTS Communication Mode Half Duplex OFF RTS Communication Mode Full Duplex 2 System Reservation Always OFF 3 System Reservation Always OFF 4 System Reservation Always OFF 5 System...

Страница 41: ... cover Card cover is attached to the product upon shipping 2 Slide the card cover to remove it 3 With the chipped edge of the SD card is in the position shown below insert the card all the way into the slot 4 Insert the catch of the card cover into the opening shown in the figure below Chipped edge Catch ...

Страница 42: ... Setup CPS PC341MB ADSC1 9201 Reference Manual Hardware 42 5 Fasten with a screw Reverse the procedure described in the Insert SD card to remove the card ...

Страница 43: ... 43 Installation This section describes how to mount the product on a DIN rail or on the wall and to connect to an external device with a cable ...

Страница 44: ...all the product in the orientations shown below 0 C Other orientations may cause problems such as malfunctions due to inadequate heat dissipation DIN rail Mounting Wall Mounting Operating ambient temperature should be between 20 C and 55 C when the product is installed on the ceiling or horizontally Ceiling installation Horizontal installation ...

Страница 45: ...e is within the specified range an operational malfunction may occur if there is other device generating high heat the radiation will influence the product to increase its temperature Do not install this product into the fully sealed space except the case in which the internal temperature is adjustable by equipment such as air conditioner Long term usage might increase the temperature of the produ...

Страница 46: ...rne est réglée par un appareil comme un climatiseur Une utilisation sur une période prolongée peut accroître la température et mener à une défaillance ou à d autres problèmes Lors de l utilisation du produit dans un environnement à température élevée la durée de vie du produit sera réduite Pour contrebalancer la température élevée procédez à un refroidissement par air pulsé 2 Mounting on Removing ...

Страница 47: ... the product on the DIN rail How to Remove 1 Pull down the hooks to unlock If the hooks are stuck use a slotted screwdriver to unlock 2 1 With the hooks unlocked pull the lower part of the product toward you 2 By lifting the product you can easily remove it from the DIN rail Fixed hooks 1 1 2 2 ...

Страница 48: ...he product CAUTION Tightening torque should be carefully controlled according to the wall on which you are installing to Installing onto the wall may not satisfy the UL standard certification ATTENTION Surveillez étroitement le couple utilisé pour serrer les vis Il doit être approprié pour le type de mur utilisé pour le montage Il est possible qu un montage mural ne satisfasse pas aux besoins de l...

Страница 49: ...a cable and insert it to the opening 2 After the insertion secure the stripped part by turning screws with a slotted driver to prevent it from disconnecting CAUTION Removing the connector plug by grasping the cable can break the wire Always grasp the connector to remove it Tightening torque of the supplied connector is described below DEGSON 0 19 N m PHOENIX CONTACT PTR MESSTECHNIK 0 25 N m Strip ...

Страница 50: ...our retirer la fiche vous risquez de briser le fil Saisissez toujours le connecteur pour le retirer Le couple de serrage pour le connecteur fourni est indiqué ci dessous DEGSON 0 19 N m PHOENIX CONTACT PTR MESSTECHNIK 0 25 N m Dénudez environ 7 mm plus ou moins 0 5 mm de la section gainée du câble pour le raccorder au connecteur ...

Страница 51: ... time for up to 12 voltage 2 milliseconds up to 30 milliseconds Cable Use copper wires that tolerate a temperature of 75 C or higher Recommended power supply is the optional product of the CPS PWD 15AW12 01 CAUTION Removing the connector plug by grasping the cable can break the wire Always grasp the connector to remove it Tightening torque of the supplied connector is described below DEGSON 0 19 N...

Страница 52: ...ection gainée du câble pour le raccorder au connecteur Si le courant de sortie maximum de l alimentation externe est moindre que le courant maximum absorbé par ce produit il y a possibilité d un dysfonctionnement en raison de l appel de courant au moment de la mise en route ou de la fluctuation de charge Le vieillissement de l alimentation externe peut provoquer un défaillance au démarrage Signal ...

Страница 53: ...7 600 900 19 200 1 200 9 600 The cable lengths in the table are not guaranteed for the communication speed The table below lists the maximum communication distances of the terminator resistor value and individual cable diameters The terminators on the product 100Ω and the terminators generally used with RS 422A 485 120Ω are listed Maximum communication distances of the terminator resistor value 10...

Страница 54: ...te bps Error 300 0 00 600 0 00 900 0 00 1 200 0 00 2 400 0 00 4 800 0 00 9 600 0 16 14 400 0 16 19 200 0 16 28 800 0 16 38 400 0 16 57 600 0 16 115 200 0 16 Half Duplex Half duplex needs two or more sets of twisted pair One set is for a signal line other free line s is are for the signal ground SG Connect TX and TX to make them as a set of twisted pair wire TX TX SG TX TX SG This product External ...

Страница 55: ...f the external device Full Duplex Full duplex needs three or more sets of twisted pair Two sets are for a signal line other free line s is are for the signal ground SG Connect TX and TX RX and RX to make them as a set of twisted pair wire TX TX RX RX SG SG RS 422A 485 5 pin connector External device This product External device TX TX RX RX SG RX RX TX TX SG ...

Страница 56: ...ble can break the wire Always grasp the connector to remove it Tightening torque of the supplied connector is described below DEGSON 0 19 N m PHOENIX CONTACT PTR MESSTECHNIK 0 25 N m Strip off approximately 7mm plus or minus 0 5mm of the covered part of a cable to connect with the connector If the shielded cables are incorrectly wire connected to the ground the shield might become an antenna picki...

Страница 57: ... m PHOENIX CONTACT PTR MESSTECHNIK 0 25 N m Dénudez environ 7 mm plus ou moins 0 5 mm de la section gainée du câble pour le raccorder au connecteur Si les câbles blindés sont mal raccordés à la mise à la terre le blindage pourrait agir comme antenne et recueillir des signaux parasites ou en émettre Si vous découvrez les sources de problèmes retirez la mise à la terre du blindage Signal de mise en ...

Страница 58: ...pecial treatment of the signal lines in the connector is required ensure that this is done in accordance with the specifications Refer to RS 232C Serial Port in the page 25 for details of the RS 232C serial port and pin assignment Connecting to an external device Example Connection to a Modem Example Connection to a PC TxD RxD RTS CTS DTR DSR SG TxD RxD RTS CTS DTR DSR SG Transmit Data Receive Dat...

Страница 59: ... the baud rate that can be set with the product Error rate differs depending on the set baud rate Baud Rate bps Error 300 0 00 600 0 00 900 0 00 1 200 0 00 2 400 0 00 4 800 0 00 9 600 0 16 14 400 0 16 19 200 0 16 28 800 0 16 38 400 0 16 57 600 0 16 115 200 0 16 External device TxD RxD RTS CTS DTR DSR SG TxD RxD RTS CTS DTR DSR SG ...

Страница 60: ...round of this product with ground of signal source by braided shield CAUTION Removing the connector plug by grasping the cable can break the wire Always grasp the connector to remove it Tightening torque of the supplied connector is described below DEGSON 0 19 N m PHOENIX CONTACT PTR MESSTECHNIK 0 25 N m Strip off approximately 7mm plus or minus 0 5mm of the covered part of a cable to connect with...

Страница 61: ...MESSTECHNIK 0 25 N m Dénudez environ 7 mm plus ou moins 0 5 mm de la section gainée du câble pour le raccorder au connecteur En l absence d un raccordement de masse analogique les données de conversion seront indéfinies Signal analogique dont l entrée positive et l entrée négative n excèdent pas le débit calorique maximum du courant de l entrée analogique S ils excèdent le maximum le produit risqu...

Страница 62: ...n the page 30 for details of the digital input counter input digital output connector and pin assignment The type of connectors in the package differs depending on the period of manufacturing To check the supplied connector type refer to Appendix Connector Check Input equivalent circuit of digital counter input interface unit is shown in the figure below DI connects to a device which can be curren...

Страница 63: ...t Corresponded to current sink output Connecting Switch Connecting the Input to the sink type output Connecting to an external device B_COM This Product External device 12V Input pin Switch Switch Input pin Opto coupler Opto coupler Vcc Vcc 12V This Product Sink type output Input pin B_COM ...

Страница 64: ...period of manufacturing To check the supplied connector type refer to Appendix Connector Check Digital output circuit DO connects to the device controlled by the current drive such as relay controlling or LED The connection requires an external power supply to deliver current ON OFF of the device controlled by the current drive is controlled by digital value The rated of output current is up to 10...

Страница 65: ... break the wire Always grasp the connector to remove it Tightening torque of the supplied connector is described below DEGSON 0 19 N m PHOENIX CONTACT PTR MESSTECHNIK 0 25 N m For wiring strip off approximately 7mm plus or minus 0 5mm of the covered part of a cable to connect with the connector About a caution mark on the product Please use copper wires that tolerate the temperature of 75 C and hi...

Страница 66: ...urs le connecteur pour le retirer Le couple de serrage pour le connecteur fourni est indiqué ci dessous DEGSON 0 19 N m PHOENIX CONTACT PTR MESSTECHNIK 0 25 N m Dénudez environ 7 mm plus ou moins 0 5 mm de la section gainée du câble pour le raccorder au connecteur Signal de mise en garde sur le produit Veuillez utiliser des fils de cuivre qui résistent à une température de 75 C Celsius et plus ...

Страница 67: ... 67 Appendix This section lists the specifications and the physical dimensions of the product and the details of model name ...

Страница 68: ...n time 74μs at 20000 Steps Hardware specifications Item CPS PC341MB ADSC1 9201 CPU ARM Cortex A8 600MHz Memory On Board 512MB DDR3 SDRAM ROM On Board 32MB NOR Flash for OS LAN Transmission standard 10BASE T 100BASE TX The number of channels 2 Connector RJ 45 Connector LED Speed Yellow Link Act Green RS 422A 485 Transmission scheme Asynchronous serial transmission Full Duplex Half Duplex Only full ...

Страница 69: ...Male LED Transmission Yellow Reception Yellow Digital input Counter input Input type Opto coupler Isolation Input Compatible with current sink output negative logic 1 Isolation Resistance Bus Isolation 500VDC Opto coupler Isolation 1000V Built in power supply 12VDC Input resistance 5 6kΩ Input ON current 1 6mA or more Input OFF current 0 16mA or less Response time Within 200μsec 2 Interrupt Digita...

Страница 70: ...ange 0 20mA Maximum input rating 30mA Input impedance 250Ω The number of channels Differential Input 2ch Channel switching rate 3msec ch Max 3 Conversion rate The sampling interval differs by the software programmed by the user Data buffer None Resolution 12bit Non Linearity error 4 10LSB Isolation Resistance Bus Isolation 500VDC Inter Channel Isolation 200V Connector 2 piece 3 5mm pitch 3 pin ter...

Страница 71: ... temperature 20 60 C 7 Non operating ambient humidity 10 90 RH No condensation Floating dust particles Not to be excessive Corrosive gases None Line noise resistance Line noise AC Line 2kV 8 Signal Line 1kV IEC61000 4 4 Level 3 EN61000 4 4 Level 3 Static electricity resistance Touch 4kV IEC61000 4 2 Level 2 EN61000 4 2 Level 2 Air 8kV IEC61000 4 2 Level 3 EN61000 4 2 Level 3 Vibration resistance S...

Страница 72: ... When you use with the CPS PWD 15AW12 01 by CONTEC instantaneous voltage drop allowed time is 20 milliseconds or less ATTENTION Si les fluctuations de la tension d alimentation sont au delà des caractéristiques du produit raccordez un transformateur à tension constante Si les signaux parasites sont importants raccordez un transformateur de séparation transformateur qui réduit les interférences Ne ...

Страница 73: ...are 73 2 Physical Dimensions CPS PC341MB ADSC1 9201 4 φ3 5 3 8 mm 188 78 66 4 170 154 55 30 5 20 4 26 LAN A 12 24VDC COM A RESET SW1 SD LAN B Isolated R S 422A 485 AI1 AI0 DI CNT SHUT DO0 DO1 COM B USB R S 232C TERM Half Full MODE Half Full ON OFF SW2 DOWN ...

Страница 74: ... Cortex A8 2 Memory 4 512M Byte 3 Version 1 The 1st Model 4 Function MB Modbus Master 5 Interface A Analog I O D Digital I O S Serial S 232C RS 422A 485 C Counter 6 Numbering of the Interface 1 The 1st Model 7 OS 9 Linux OS Built in battery type 8 ROM 2 32MB 9 Application 01 OPC UA Server CPS PC 3 4 1 MB ADSC1 9 2 0 1 CONPROSYS Series 1 2 3 5 7 8 6 4 Soft PLC Type 9 ...

Страница 75: ...posing of the product follow the instruction below and remove the battery 1 Remove the five screws from bottom of the product to remove the cover See the figure below 2 Remove the cover 3 Cut the two holding metals with nippers and take off the battery CAUTION When disposing of the battery please comply with your local municipal regulations and ordinances ATTENTION Respecter les règles et les ordo...

Страница 76: ...Green 0 25 N m Connector type Socket MC1 5 3 G 3 5 Green Connector type Plug DEGSON 15EDGK 3 5 03P 14 1000AH Green 0 19 N m Connector type Socket 15EDGRC THR 3 5 03P 13 Black 5pin Connector Connector type Plug PTR MESSTECHNIK AK1550 5 3 5 GREEN Green 0 25 N m Connector type Socket STL1550 5G 3 5 H GREEN Green Connector type Plug DEGSON 15EDGK 3 5 05P 14 1000AH Green 0 19 N m Connector type Socket ...

Страница 77: ...25 N m Type de connecteur broche MC1 5 3 G 3 5 Vert Type de connecteur enfichable DEGSON 15EDGK 3 5 03P 14 1000AH Vert 0 19 N m Type de connecteur broche 15EDGRC THR 3 5 03P 13 Noir Connecteur à 5 broches Type de connecteur enfichable PTR MESSTECHNIK AK1550 5 3 5 GREEN Vert 0 25 N m Type de connecteur broche STL1550 5G 3 5 H GREEN Vert Type de connecteur enfichable DEGSON 15EDGK 3 5 05P 14 1000AH ...

Страница 78: ... 78 Optional Products This section lists optional items that can be used along with the product ...

Страница 79: ...ws Acquire them as required Product Name Model type Description DIN rail fitting power supply CPS PWD 15AW12 01 Fitting power supply 15W Input 100 240VDC Output 12VDC 1 3A SD Card SD 4GB A SD card 4GB Magnet CPS MAG01 4 Magnet Four Piece Set Visit the Contec website for the latest optional products Website https www contec com ...

Страница 80: ... 80 Customer Support and Inquiry CONTEC provides the following support services for you to use CONTEC products more efficiently and comfortably ...

Страница 81: ...fers the useful information including product manuals that can be downloaded through the CONTEC website Download https www contec com download You can download updated driver software firmware and differential manuals in several languages Membership registration myCONTEC is required to use the services ...

Страница 82: ... 82 Index ...

Страница 83: ...9201 Reference Manual Hardware 83 Revision History MONTH YEAR Summary of Changes April 2016 The First Edition April 2018 Changed the layout of the manual September 2018 Additional information was listed due to some parts change ...

Страница 84: ...5 Japan https www contec com No part of this document may be copied or reproduced in any form by any means without prior written consent of CONTEC CO LTD CPS PC341MB ADSC1 9201 Reference Manual Hardware NA04998 LYTY338 08302019_rev8 04252016 August 2019 Edition ...

Отзывы: