Troubleshooting
—
CPSA-PCB100 Reference Manual
—
101
—
1.
Troubleshooting
When the product does not function properly, perform the following checks
1.
In general
Check the LEDs on the front panel
Check that PWR LED is on.
Check that ST1 LED is flashing.
Check the network port LEDs.
Check the LEDs on the UTP connector at the front of the product.
If the network cable is correctly connected to a hub, the Link/Act LED will be on.
If not, refer to the
and confirm HUB or LAN cable. The Link/Act LED will be
on when communication is in progress via the network port
Use the ping command from a host computer and see
whether the server unit responds.
Ping the IP address of the server unit.
The server unit should respond if it is operating.
Example:
The following response should be received when the server unit is set to IP address 10.1.1.101:
ping 10.1.1.101<Enter> :
Reply from 10.1.1.101: bytes=32 time<10ms TTL=255
Reply from 10.1.1.101: bytes=32 time<10ms TTL=255
Reply from 10.1.1.101: bytes=32 time<10ms TTL=255
If you are unsure of the IP address, you can restore the default factory settings
(IP address 10.1.1.101) by turning on the power to the product with SW1-2 switch on (left).
CAUTION
If you set the switch back to the former position, the product starts with the settings
previously saved in ROM.
Содержание CONPROSYS Alpha Series
Страница 31: ...31 CONPROSYS WEB Setting This chapter describes the product system and functions...
Страница 47: ...47 PLC Backup This section describes PLC Backup menu and each of the setting procedure...
Страница 100: ...100 Troubleshooting This section describes how to solve the troubles when the product does not function properly...
Страница 109: ...Appendix CPSA PCB100 Reference Manual 109 2 Physical Dimensions mm 94 7 5 1 44 7 124 8 14 Open Lock 4 18...
Страница 119: ...119 Index...