background image

 

3

 

 

Prior to installation the maximum comfort temperature must be set by using the knob marked COMF located at 
the back of the controller as shown below. The range is 15

ƒ

C to 35

ƒ

C. The maximum comfort temperature limits 

the room temperature that can be set by users after installation. The required room temperature can be 
reduced by users by using the two adjustment buttons on the front of the controller after installation. These 
buttons allow the user to change the set room temperature up or down subject to not exceeding the maximum 
temperature set prior to installation. 
After pressing the on button the heating will operate until the set room temperature is achieved, at this point the 
indicator lights around the on button will change from green to orange. When the room temperature drops the 
heating will become active again and the indicator lights will change back to green. 
The display screen will show the actual room temperature, except briefly when either of the two adjustment 
buttons are pressed, the new target room temperature is then temporarily displayed.  This will flash to show you it 
is the target temperature and not the room temperature.   

3. Temperature Control Mode 

Temperature control for Comfort period

 

Room temperature below the set temperature. 
Heating is active. 

Variable resistors to set 
maximum comfort and 
setback temperatures 

Set temperature 
achieved 

Temperature control for comfort and setback periods can be used individually or together. This can also be used in 
conjunction with the timer mode options. 

In this mode, the controller will set heating active when the room temperature drops 
below the set temperature. This feature can be used for frost protection or in situations 
where a minimum room temperature must be maintained. The setback temperature 
can be set using the knob marked SETB mounted on the back of the unit as shown 
above. This can be set from 0ºC - 15ºC.

 

Temperature control for Setback period

 

For this mode, the switches are set as shown below. 

If the heating is active in the setback mode, the indicators will illuminate red and green. 

4. Changing temperature or timer settings after installation 

The temperature and/or timer settings can be changed after installation. It is important to switch the power off to 
the controller before the changes are made. After the changes are made and the power is restored the new 
settings will take effect. 

The controller can be switched off using any external device with voltage free 
contacts. For example, timers or a building management system. 

If this function isn’t used, a wire link across the external input connectors must be 
used.  

When the external input connection is open, the indicators will light up red and the 
heating will be disabled. However, setback mode will still operate at low 
temperature. 

5. External Input 

Отзывы: