52
11
TECHNICAL DATA
The following applies for all the models of the device:
/
The water to be filtered must conform to the European Drinking Water Regulations!
/
Nominal flow rate after backwashing at a pressure loss of 0.2/0.5 bar as given in the table below.
/
The nominal pressure denotes the pressure class, according to which the filter must fulfill the require-
ments of the standards DIN EN 13443-1 and DIN 19628. The maximum operating pressure is lower,
in order to ensure the optimum function of the backwashing filter.
11.1
ACCESSORIES
/
Clear 2.0 Automatic controls retrofit kit
. For subsequent upgrade of the manual backwashing filter
to an automatic backwashing filter.
/
Clear 2.0 SAFE
. Central water monitoring system for installation between built-in rotary flange and
backwashing filter. For monitoring the water consumption and shutting off the water pipe when ad-
justable limits are exceeded. Protects against the effects of water pipe bursts, leakages, defects on the
domestic water installation and unusually high water consumption. Detects leaking taps and valves.
Technical data
CLEAR 2.0 R ¾"
CLEAR 2.0 R 1"
CLEAR 2.0 R 1¼"
Connection diameter nominal
DN 20
DN 25
DN 32
Nominal flow rate at a pressure loss
of 0.2/0.5 bar (20/50 kPa)
2.8/4.6 m³/h
3.2/5.1 m³/h
3.4/5.8 m³/h
Backwashing volumetric flow
1)
1) Applies for a completely opened flushing water valve and 2 - 3 bar (
200 - 300 kPa
) mains pressure.
approx. 0.3 l/s
approx. 0.3 l/s
approx. 0.3 l/s
Nominal pressure
PN 16
PN 16
PN 16
Operating pressure
1.5 - 10 bar
(150 - 1000 kPa)
1.5 - 10 bar
(150 - 1000 kPa)
1.5 - 10 bar
(150 - 1000 kPa)
Mesh size
lower mesh width
upper mesh width
0.1 mm (100
μ
m)
0.095 mm (95
μ
m)
0.125 mm (125
μ
m)
0.1 mm (100
μ
m)
0.095 mm (95
μ
m)
0.125 mm (125
μ
m)
0.1 mm (100
μ
m)
0.095 mm (95
μ
m)
0.125 mm (125
μ
m)
Water and ambient temperature
max. 30 °C (86 °F)
max. 30 °C (86 °F)
max. 30 °C (86 °F)
Fitting length with screw connection 180 mm
195 mm
230 mm
Fitting length w/o screw connection
100 mm
100 mm
110 mm
Threaded connection according to
DIN EN 10226-1
DIN EN 10226-1
DIN EN 10226-1
Weight
3.4 kg
3.6 kg
4.1 kg