Operation Manual
Regulator
4 kW 560 V DC 40% Duty Cycle + 24 V DC
BAL9100-0126d-EN
www.conductix.com
original document
page 15 of 32
7.4.3
Example: Interface is not used
Even if signals available through the interface plug are not being used, it is still
necessary to connect pin 1 to pin 4 for the
Regulator to start
. See also chapter 8.1 for more information on this subject.
Pilot pins are not designed to be used as an ON/OFF switch and it is thus recommended not to open the pilot connection under
load. However, disconnecting the pilot pins will reset the Regulator. Therefore, this procedure can be used to reset a fault in case
of automatic shutdown. This is the purpose of the switch shown in the following illustration, connecting pins 11 and 12 on the load
side. Refer to chapter 0 for more information.
Voltage present on the pilot pins is not isolated from the main output power. Make sure to use a switch with suitable isolation to
ground. Rating between contacts is 24 V DC / 150mA.
Initial status of relays, please see chapter 10.