Operation Manual
Regulator
4 kW 560 V DC 40% Duty Cycle + 24 V DC
BAL9100-0126d-EN
www.conductix.com
original document
page 10 of 32
4.5
Electrical Connections
•
X1 - AC Input
Refer to chapter 14 for information on Pickups
•
X2 - DC Power outputs
HAN Q4/2 (Harting) or CQM04/2 (Ilme)
•
X3 - Interface
SACC-E-M12FS-8CON (Phoenix) or series 763/8-pole (Binder)
Connection cables can be ordered separately. Refer to chapter 14.
4.5.1
Connection of Power Input: X1
The power input of the Regulator must be connected to a suitable Pickup. The use of an extension cable between the Regulator
and the Pickup is generally not allowed. Refer to paragraph 14 for information on Pickups.
4.5.2
Connection of Power Outputs: X2
(view: contact side)
PIN 1
> DC+ out
PIN 3
> DC- out
(Power output 560 V DC)
PIN 2
> 24 V DC
PIN 4
> 0 V DC
(Isolated 24 V / 5 A DC power output)
this 24V/5A output is different from the 24V/150mA available on the interface plug X3
PIN 11
> Pilot 1
PIN 12
> Pilot 2
(Pilot 1 and 2 must be shorted for the device to power up – see chapter 7.4, 8.1 and 8.2)
PIN
> Ground