Nortec EL

Mounting continued...

Standard Mounting

1.  Locate 2×4 wooden studs or equivalent support in the mounting 

surface, and mark the attachment points “A” and “B” at the desired 

position with the help of a level.

2.  Install 1/4×2 in lag bolts (supplied by others) at attachment points 

“A”. Use longer screws if going through drywall or other structural 

material into the mounting surface. Allow the heads of the screws 

to extend 0.25 in (5 mm) from the mounting surface so that the 

humidifier can be installed on the bolts.

3.  Remove the door panels from the humidifier.
4.  Carefully raise and install the humidifier onto the installed lag bolts.
5.  Align the humidifier with the help of a level, then tighten the lag bolts.
6.  Install additional lag bolts (supplied by others) into the mounting 

surface at attachment points “B”, and fasten securely.

7.  Reinstall the door panels, and fasten them securely.

Refer to “Mounting the Humidifier” in the Installation Manual (Condair 

document number 2582302) for other mounting arrangements, including 

OSHPD (seismic) mounting arrangement.

WARNING!

Heavy object – risk of injury!

 The small humidifier weighs 45 lb 

(20 kg), and the large humidifier weights 120 lb (54 kg). Use an 

appropriate lifting device, or request assistance to raise the humidifier 

into position.

Dimension

Housing Size

Small

Medium

Large

X

12.0 in

(305 mm)

16.0 in

(406 mm)

16.0 in

(406 mm)

Y

17.6 in

(446 mm)

20.7 in

(526 mm)

16.8 in

(426 mm)

X

A

A

A

B

B

B

X

Y

1

Large Nortec EL humidifier shown.

1  Lag bolt

Содержание Nortec EL005

Страница 1: ...r Overview 2 Mounting 3 Installation Requirements 3 Standard Mounting 4 Steam Distribution 5 Installation Requirements 5 Plumbing 6 Water and Drainage Requirements 6 Electrical 7 Installation Requirements 7 External Power Connections 7 Safety Chain and Control Signal Connections 8 2583578_B_EN_1811_Nortec EL_QSG ...

Страница 2: ... humidistat used for control of the space in the return duct high limit in the supply duct 3 On Off humidistat used for humidity control 4 Steam line 5 Electrical disconnect high voltage supply 6 Drain line 7 Air gap funnel with optional trap 8 Water supply 9 Condensate line 10 Steam distributor 11 Air proving switch external safety chain 12 Supply air duct 13 Return air duct ...

Страница 3: ...surfaces that can freeze or near vibrating components or on the floor In addition the mounting surface must be able to withstand temperatures of 140 158 F 60 70 C that can be generated during operation of the humidifier 6 Thehumidifiershouldbemountedonawallorothersuitablesurface that offers a sufficiently high load bearing capacity 7 The Nortec ELhumidifier should be installed in a drip proof loca...

Страница 4: ...g bolts 5 Alignthehumidifierwiththehelpofalevel thentightenthelagbolts 6 Install additional lag bolts supplied by others into the mounting surface at attachment points B and fasten securely 7 Reinstall the door panels and fasten them securely Refer to Mounting the Humidifier in the Installation Manual Condair documentnumber2582302 forothermountingarrangements including OSHPD seismic mounting arran...

Страница 5: ... the steam line 11 Upon completion of installation purge the steam and condensate lines to remove any contaminants or construction material 12 Prime the condensate traps with water Refer to Steam Line Connections in the Installation Manual for other details 10 o 2o 12 in 300 mm 2 in 50 mm 12 in 300 mm in 12 mm Minimum Upslope Minimum Downslope 1 2o 1 in 25 mm 48 in 1 2 m 1 2o 1 in 25 mm 48 in 1 2 ...

Страница 6: ...ne with a minimum internal diameter of 7 8 in 22 mm and secured with clamps 7 The drain line should be as short as possible and have a constant minimumdownslopeof1in 48in 1 2 tothefunnelwithouttouching its sides or bottom Use stainless steel or plastic pipe suitable for temperatures up to 212 F 100 C 8 Drain lines from large humidifiers with dual steam cylinders must empty into separate air gap fu...

Страница 7: ...tallation work has been completed 4 All cables must enter the control cabinet in the humidifier through appropriatecableglandsorgrommets andmustbeproperlysecured to prevent fraying or become a tripping hazard Referto ElectricalConnections intheInstallationManualforotherdetails DANGER Risk of electric shock The Condair humidifier is mains powered and should only be wired by a licensed electrician C...

Страница 8: ... signal can be connected to terminal point 5 and 3 using terminal point 3 as common Note If the cable shielding is already connected to a potential or a grounded conductor do not connect it to terminal point 3 4 If a 24 V On Off humidistat is used connect the input to the terminal points 4 and 6 onthelowvoltageterminalstrip Whenconnecting a 24 V On Off humidistat set the jumper JP1 on the driver b...

Страница 9: ...Notes ...

Страница 10: ...e with local and national electrical code requirements by a licensed electrician All water supply and drain line connections must be installed in accordance with local plumbing codes by a licensed plumber Condair does not accept any liability for installations of humidity equipmentinstalledbyunqualifiedpersonnelortheuseofparts com ponents equipment that are not authorized or approved by Condair US...

Отзывы: