Nortec EL

Steam Distribution

Installation Requirements

1.  Use steam line made of copper or stainless steel tube exclusively, 

or use a Condair steam hose for short distances. Steam line made 

of any other material may adversely affect the operation of the 

humidifier, and will void the warranty. Refer to the table below for 

steam line sizing.

2.  To prevent excessive backpressure in the steam cylinder, the steam 

line must not have any restrictions.

3.  The steam line must run straight up from the humidifier minimum 

12 in (300 mm) before any bends. 

4.  The steam line must have a constant slope – minimum upslope of 

10°, or minimum downslope of 2°.

5.  Do not merge steam lines, except at the steam distributor. Use a 

Condair adaptor designed for the purpose.

6.  Insulate the steam line with minimum 1 in (25 mm) pipe insulation. 
7.  Support the steam line so there is no load on the humidifier.

8.  Install condensate lines at all low points and horizontal-to-vertical 

transitions in the steam line. The condensate line should always 

connect to a full size “Tee” connector, and have a minimum con-

stant downslope of 1.2°. The trap should be located minimum 12 in 

(300 mm) below the connector, and have a minimum height of 8 in 

(200 mm). 

9.  Use 3/8 in (9.5 mm) Condair condensate hose, or 1/4 in (6.5 mm) 

Med-L  copper  tube  or  3/8  in  (9.5  mm)  stainless  steel  tube  for 

condensate traps.

10.  Install condensate traps every 15 ft (4.5 m) in the steam line.
11.  Upon completion of installation, purge the steam and condensate 

lines to remove any contaminants or construction material.

12.  Prime the condensate traps with water.

Refer to “Steam Line Connections“ in the Installation Manual for other 

details.

10

o

2

o

12 in
(300 mm)

2 in
(50 mm)

12 in
(300 mm)

½ in
(12 mm)

Minimum Upslope

Minimum Downslope

1.2

o

1 in
(25 mm)

48 in
(1.2 m)

1.2

o

1 in
(25 mm)

48 in
(1.2 m)

Min.

12 in

(300 mm)

8 in

(200 mm)

Min.

12 in

(300 mm)

8 in

(200 mm)

Minimum
Downslope

Minimum
Downslope

Nortec 

EL 

Model

Steam Line Sizing

Maximum Equiv. 

Length

MED-L

Copper Tube

Stainless Steel Tube

Steam Losses

EL005

7 ft (2 m)

3/4 in

(20 mm)

7/8 in × 0.049 wall

(22  mm × 1.25 mm wall)

0.06 lb/h/ft

(0.09 kg/h/m)

EL010

12 ft (3.5 m)

EL020

17 ft (5 m)

EL030

22 ft (6.5 m)

EL050

43 ft (13 m)

1-1/2 in

(40 mm)

1-3/4 in × 0.065 wall

(45 mm  × 1.65 mm

wall)

0.11 lb/h/ft

(0.18 kg/h/m)

EL075

EL100

47 ft (14 m)

EL150*

EL200*

50 ft (15 m)

1-1/2 in

(40 mm)

1-3/4 in × 0.065 wall

(45  mm × 1.65 mm wall)

Condair Steam Hose

EL005-

EL030

10 ft

(3 m)

P/N 1328810 – 7/8 in (22 mm)

0.1 lb/h/ft

(0.15 kg/h/m)

EL050-

EL200

10 ft

(3 m)

P/N 1328820 – 1-3/4 in (45 mm)

0.15 lb/h/ft

(0.22 kg/h/m)

* Use a single steam line for each steam cylinder. Do not combine lines except at a 

distributor, and only if using the steam cylinders in parallel.
Refer to the Installation Manual for over-sized steam lines for longer steam runs.

WARNING!

Risk of serious injury or damage to equipment!

 

Restrictions in the steam line can cause excess build-up 

of  backpressure which can result in serious burn injuries 

or damage to equipment. Backpressure should not exceed 

5.5 in H2O (1.36 kPa).

Содержание Nortec EL005

Страница 1: ...r Overview 2 Mounting 3 Installation Requirements 3 Standard Mounting 4 Steam Distribution 5 Installation Requirements 5 Plumbing 6 Water and Drainage Requirements 6 Electrical 7 Installation Requirements 7 External Power Connections 7 Safety Chain and Control Signal Connections 8 2583578_B_EN_1811_Nortec EL_QSG ...

Страница 2: ... humidistat used for control of the space in the return duct high limit in the supply duct 3 On Off humidistat used for humidity control 4 Steam line 5 Electrical disconnect high voltage supply 6 Drain line 7 Air gap funnel with optional trap 8 Water supply 9 Condensate line 10 Steam distributor 11 Air proving switch external safety chain 12 Supply air duct 13 Return air duct ...

Страница 3: ...surfaces that can freeze or near vibrating components or on the floor In addition the mounting surface must be able to withstand temperatures of 140 158 F 60 70 C that can be generated during operation of the humidifier 6 Thehumidifiershouldbemountedonawallorothersuitablesurface that offers a sufficiently high load bearing capacity 7 The Nortec ELhumidifier should be installed in a drip proof loca...

Страница 4: ...g bolts 5 Alignthehumidifierwiththehelpofalevel thentightenthelagbolts 6 Install additional lag bolts supplied by others into the mounting surface at attachment points B and fasten securely 7 Reinstall the door panels and fasten them securely Refer to Mounting the Humidifier in the Installation Manual Condair documentnumber2582302 forothermountingarrangements including OSHPD seismic mounting arran...

Страница 5: ... the steam line 11 Upon completion of installation purge the steam and condensate lines to remove any contaminants or construction material 12 Prime the condensate traps with water Refer to Steam Line Connections in the Installation Manual for other details 10 o 2o 12 in 300 mm 2 in 50 mm 12 in 300 mm in 12 mm Minimum Upslope Minimum Downslope 1 2o 1 in 25 mm 48 in 1 2 m 1 2o 1 in 25 mm 48 in 1 2 ...

Страница 6: ...ne with a minimum internal diameter of 7 8 in 22 mm and secured with clamps 7 The drain line should be as short as possible and have a constant minimumdownslopeof1in 48in 1 2 tothefunnelwithouttouching its sides or bottom Use stainless steel or plastic pipe suitable for temperatures up to 212 F 100 C 8 Drain lines from large humidifiers with dual steam cylinders must empty into separate air gap fu...

Страница 7: ...tallation work has been completed 4 All cables must enter the control cabinet in the humidifier through appropriatecableglandsorgrommets andmustbeproperlysecured to prevent fraying or become a tripping hazard Referto ElectricalConnections intheInstallationManualforotherdetails DANGER Risk of electric shock The Condair humidifier is mains powered and should only be wired by a licensed electrician C...

Страница 8: ... signal can be connected to terminal point 5 and 3 using terminal point 3 as common Note If the cable shielding is already connected to a potential or a grounded conductor do not connect it to terminal point 3 4 If a 24 V On Off humidistat is used connect the input to the terminal points 4 and 6 onthelowvoltageterminalstrip Whenconnecting a 24 V On Off humidistat set the jumper JP1 on the driver b...

Страница 9: ...Notes ...

Страница 10: ...e with local and national electrical code requirements by a licensed electrician All water supply and drain line connections must be installed in accordance with local plumbing codes by a licensed plumber Condair does not accept any liability for installations of humidity equipmentinstalledbyunqualifiedpersonnelortheuseofparts com ponents equipment that are not authorized or approved by Condair US...

Отзывы: