Modbus Installation |
34
Variable
Name
Description
Addr
Type
Format
Range
Unit
R/W
Additional Details
1 = Service
Required
Status
Read humidification status
30302
Input
Register
Binary
0,1
-
Read
0 = Idle / Standby
1 = Active /
Humidifying
Connecti
on
Read connection status
40267
Input
Register
Binary
0,1
-
Read
0 = Communication
Error
1 = Normal
Communication
HourOpt Read operational hours of unit
30350
Input
Register
Analog
0 -
Infi
nity
hrs
Read
Displays hours of
operation.
KeepWar
m
Read keepwarm option status
(enable/disable at humidifier)
30356
Input
Register
Analog
0,1
-
Read
Bit0 - KEEPWARM
0 = Disabled
1 = Enabled
3DayDrai
n
Read 3 day drain option status
(enable/disable at humidifier)
30356
Input
Register
Analog
0,1
-
Read
Bit1 - 3 DAY DRAIN
0 = Disabled
1 = Enabled
SysDema
nd
Read system output / demand
30347
Input
Register
Analog
0-
100
%
Read
Displays output as
percentage of
capacity
ServHour
s
Read hours before next
service
30352
Input
Register
Analog
500
-0
hrs
Read
Displays hours
remaining until next
service.
SecurityL
oop
Displays status of security
loop.
30364
Input
Register
Analog
0,1
-
Read
Displays the status
of the security loop
on terminals 1 and
2. Loop must be
"closed" for
humidifier to
operate.
0 = Open
1 = Closed
Содержание Modbus RTU
Страница 9: ...Modbus Installation 6 Figure 3 EL NH EL Modbus Wiring Diagram ...
Страница 10: ...7 Modbus Installation Figure 4 TC Modbus Wiring Diagram ...
Страница 11: ...Modbus Installation 8 Figure 5 MES2 and RH2 Modbus Wiring Diagram ...
Страница 12: ...9 Modbus Installation Figure 6 NHRS Modbus Wiring Diagram ...
Страница 43: ...Modbus Installation 40 The following points may be mapped for control ...
Страница 44: ...41 Modbus Installation Table 8 MES2 and RH2 Humidifier Modbus Parameters ...
Страница 52: ...49 Modbus Installation Troubleshooting Table 10 General Troubleshooting ...
Страница 59: ...Modbus Installation 56 Figure 13 Low voltage terminal strip on NHRS Humidifier ...