45 |
Modbus Installation
CtrlStatus1
Describes
controller
hardware
and jumper
statuses.
30109
Input
Register
Integer
0-
32768
-
Read
Uses significant bits 0
through 15 (1, 2, 4, 8, 16,
32, 64, 128, 256, 512,
1024, 2048, 4096, 8192,
16384, 32768 respectively).
Bit 1 - Electrodes passing
current (0 = On)
Bit 2 - FAULT Relay (0 = On)
Bit 3 - YELLOW LED
(1 = Illuminated)
Bit 4 - GREEN LED
(0 = Illuminated)
Bit 5 - FAN (1 = On)
Bit 8 - High Water Input
(0 = High Water)
CtrlStatus2
Hardware
status
Port D_E
30110
Input
Register
Integer
0-
32768
-
Read
Bit 4 - MODBUS Control
Active
(0 = J26 installed)
Bit 9 - FILL (1 = Active)
Bit 10 - DRAIN (1 = Active)