A Trigger command supplied by the Alarm Control Panel, or equivalent, in the form of an N/C
(Normally closed) or an N/O (Normally open) relay changing state when the Alarm system
confirms an intruder alert.
2.1 POSITIONING
The Smoke Screen should ideally be sited in a covert position away from prying eyes and thereby
reducing the possibility of tamper or an attack. The ideal place for the Smoke Screen is above a
ceiling from where the smoke plume is used to its best effect, bursting on the ground and
spreading outwards and upwards through 360°. If no suitable ceiling location is available then the
next best location is a wall mounting as close to ceiling height as possible.
Wall-mounting.
The optimum wall mounting position for the Smoke Screen is 2.5 metres above the floor facing the
area to be protected and using an appropriate angle nozzle. The maximum recommended
mounting-height above floor level is 3 metres, the minimum is 1 metre and there should be no
obstacle within 1 metre of the smoke output nozzle.
Ceiling-mounting.
The optimum ceiling mounting height for the Smoke Screen is 2.5 metres above the floor over the
area to be protected and using a straight nozzle. The maximum recommended mounting-height
above floor level is 3 metres and there should be no obstacle within 1 metre of the smoke output
nozzle.