6.1 TESTING
Full alarm test.
Where possible a full alarm test should be conducted to check that all inputs, outputs
and wiring connections to the Smoke Screen are correct. If a PIR or other detector is fitted the Smoke
Screen will fire for the designated Smoke Time period once the ‘Set’, ‘Trigger’ and ‘Hold Off’ (if fitted)
contacts are open. It will stop producing smoke if the ‘Set’ contacts are closed.
7.1 LED AND SOUND INDICATIONS
The Smoke Screen provides on-board status monitoring via an LCD, 4 x LED and an audio siren output
connection. LED indications displayed are:
LED
LED Colour
Audio
siren alarm
Relay status change
Indication Meaning
Operation
●
Flashing
Nil.
Nil.
Smoke Screen heating to
operating temperature
●
Steady
Nil.
Ready output to ok.
Smoke Screen at operating
temperature and status ok.
Triggering
●
Steady
On.
Smoke verification
output.
Smoke Screen producing
smoke.
Fault
●
Flashing
On.
Ready output to alarm.
Smoke Screen critical fault.
Isolate
●
Steady
On
Ready output to alarm
Smoke Screen is isolated by
software setting or Z6
Fault indications will automatically clear once resolved.