![Conair A1-1.5 Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/conair/a1-1-5/a1-1-5_user-manual_2649037056.webp)
●
●
Daily, or as often as needed
❒
❒
Checking electrical connections
Make sure electrical connections are properly seated.
See
Checking Electrical Connections
, in the
Maintenance section.
❒
❒
Checking process fluid level in the pump tank
Check the process fluid level in the water level gauge
on the back of the chiller. If low, see
Filling the
Chiller
, in the Installation section.
❒
❒
Verifying pump discharge pressure
While the pump is running, check that the pump pres-
sure gauges read the correct dischrge pressure. To
change the pressure adjust the From Process valve.
❒
❒
Inspecting piping for leaks
Check to see that pipes are not leaking. Look for
standing water on the floor or inside the chiller cabi-
net.
❒
❒
Inspecting the condenser coil for debris
(air-cooled models only) Remove the wire mesh side
panel in front of the condenser coil. See
Cleaning the
Air-cooled Condensers,
in the Maintenance section
●
●
Weekly, or as often as needed
❒
❒
Checking temperature and pressure readings
Check the temperature and pressure display on the
control screen, and the pump pressure gauge to ensure
they indicate normal operation.
❒
❒
Checking efficiency
Review the performance data on the Maintenance Log
found in the Appendix. If you notice a decrease in effi-
ciency over time, check all heat transfer surfaces of the
evaporator and condenser for fouling. Clean as needed.
❒
❒
Checking refrigerant sight glass
There should not be any bubbles unless the hot gas
bypass is cycling. See
Checking Refrigerant Charge
, in
the Maintenance section.
❒
❒
Checking reservoir level
Check the water level gauge on the back of the chiller.
If fluid level is low, fill. See
Checking Reservoir Level
,
in the Maintenance section.
P
REVENTATIVE
M
AINTENANCE
S
CHEDULE
Series 1 Portable Chillers, PLC Control
UGH017/0500
5-4
M
AINTENANCE
To maintain the best perfor-
mance, follow the mainte-
nance schedule and record
information in the
Maintenance Log in the
Appendix.