S
ETTING
F
AN
S
ETPOINTS
Series 1 Portable Chillers, PLC Control
UGH017/0500
4-14
O
PERATION
For the Air-cooled Chillers you can choose the pressure, in
pounds per square inch, at which the fans cycle. To set the Fan
Setpoints from the main screen:
Press the Setup arrow.
Press the Scroll arrows to scroll through the
Setup screens. Stop when you get to the PID Reset
screen.
Press the Fans arrow.
3
2
1
STATUS SETUP RUN ALM
Press arrow
PID Reset FANS
A screen displays asking for the password. Use the
Keypad to enter the password and then press the Enter
button. The Fan Setpoint screen displays:
This screen is password
protected. You must
have clearance to enter
and change this setting.
Press arrow
Fan 1
ON
25
0
limits
OFF
190
number
flashes
The screen shows the upper and lower pressure limits for
Fan 1 (the pressure, in PSI, when the fans turn on and
off). The ON pressure flashes. Use the keypad to change
this number. Then press the Enter button to save the new
number. Set from 190 PSI to 300 PSI.
Press the Scroll arrow to move to
the OFF setting. The OFF number flashes:
4
Fan 1
ON
245
limits
OFF
19
0
number
flashes
Use the keypad to change the OFF number.