background image

- 7 -

It is possible to switch between the modes By pressing the 

 or 

 buttons. To save this setting, wait 

after 

the last key press approx. 6 seconds. The display will then return to the state (on/off) from which 

you entered the mode selection menu after a few flashes and the settings will be saved.

3.2. Selection of switching sensitivity

The pump controller in modes F1 and F2 switches the output according to the measured temperature 

and switching sensitivity. In these modes, it is possible to change the switching sensitivity. By select

-

ing this value, you can specify how much the device switches the connected pump on/off below/above 

the set temperature. The lower this value is, the more constant the temperature of the circulating fluid 

will be. The switching sensitivity can be set between ± 0.1 °C and ± 15.0 °C (in 0.1 °C steps). Except 

some special cases, we recommend setting ± 1.0 °C (factory default setting). See Chapter 4 for more 

information on switching sensitivity.

To change the switching sensitivity, when the pump control is switched ON, in F1 or F2 mode, press 

and hold the   button for approximately 2 seconds until the „

d 1.0

” (factory default) appears on the 

display. By pressing the   and 

 buttons you can change this value in increments of 0,1 °C within the 

range of ±0,1 °C and ±15,0 °C. 
To exit and save the setting, wait for approx. 4 seconds. The device then returns to its defau

lt state.

Содержание WPR-100GC

Страница 1: ...COMPUTHERM WPR 100GC Pump controller with wired temperature sensor Operating Instructions...

Страница 2: ...age of 230 V or other electrical appliance within the load capacity limits can be easily controlled The pump controller is responsible for turning the pump on and off at the set and measured temper at...

Страница 3: ...g to set temperature and the switching sensitivity 1 LOCATION OF THE DEVICE It is recommended to place the pump controller near the heat ing cooling pipe or boiler on which the control is based so tha...

Страница 4: ...is displayed when the output of the appliance is switched on Make sure that the wires are properly connected and that that there is no risk of electric shock or short circuit Connect your device as fo...

Страница 5: ...zivatty szivatty vez rl Warning Always take into account the loadability of the controller relay when connecting 10 A 3 Inductive load and follow the instructions of the manufacturer of the pump which...

Страница 6: ...s turned on if the measured temperature is higher than the set temperature The switching sensitivity is taken into account when switching F2 Control of a cooling system s circulating pump the output i...

Страница 7: ...ches the connected pump on off below above the set temperature The lower this value is the more constant the temperature of the circulating fluid will be The switching sensitivity can be set between 0...

Страница 8: ...the function is on the output will turn on every 5 days for 15 seconds if the output has not been turned on in the last 5 days During this time will appear on the display instead of the measured temp...

Страница 9: ...e measured temperature reach es 5 C again to protect the pump and the heating system During this time the display alternates between and the measured temperature When the frost protection function is...

Страница 10: ...itching sensitivity of 1 0 C the pump connected to it switches ON and at temperatures below 39 0 C the output switches OFF the pump connected to it switches OFF In F2 mode the output switches exactly...

Страница 11: ...t accuracy 1 0 C Power supply 230 V AC 50 Hz Output voltage 230 V AC 50 Hz Loadability max 10 A 3 Inductive load Environmental protection IP40 Immersion sleeve connector size G 1 2 8x60 mm Length of h...

Страница 12: ...he requirements of standards EMC 2014 30 EU LVD 2014 35 EU and RoHS 2011 65 EU Manufacturer QUANTRAX Kft H 6726 Szeged F lem le u 34 Telefon 36 62 424 133 Fax 36 62 424 672 E mail iroda quantrax hu We...

Отзывы: