- 10 -

4. OPERATION OF THE INSTALLED PUMP CONTROLLER

In operating modes F1 and F2, the pump controller controls the device connected to it (eg. a pump) 

based on the temperature it measures and the set temperature, taking into account the set switching 

sensitivity (factory default ±1.0 °C). This means that if the pump controller is set to F1 mode (heat

-

ing system circulating pump control) and 40 °C, the 230 V will appear at the controller’s output at a 

temperature above 41.0 °C at a switching sensitivity of ±1.0 °C (the pump connected to it switches 

ON) and at temperatures below 39.0 °C the output switches OFF (the pump connected to it switches 

OFF). In F2 mode, the output switches exactly the opposite way. You can adjust the set temperature 

with the   and   buttons.

In F3 mode, the output is permanently ON/OFF according to the setting, regardless of the measured 

temperature in F3 mode. You can change between ON and OFF by using the

   and 

 keys.

During normal operation, the device always displays the currently measured temperature on its dis

-

play in all three operating modes. The device indicates the ON/OFF status of its output by means of 

the LED above the display.

Содержание WPR-100GC

Страница 1: ...COMPUTHERM WPR 100GC Pump controller with wired temperature sensor Operating Instructions...

Страница 2: ...age of 230 V or other electrical appliance within the load capacity limits can be easily controlled The pump controller is responsible for turning the pump on and off at the set and measured temper at...

Страница 3: ...g to set temperature and the switching sensitivity 1 LOCATION OF THE DEVICE It is recommended to place the pump controller near the heat ing cooling pipe or boiler on which the control is based so tha...

Страница 4: ...is displayed when the output of the appliance is switched on Make sure that the wires are properly connected and that that there is no risk of electric shock or short circuit Connect your device as fo...

Страница 5: ...zivatty szivatty vez rl Warning Always take into account the loadability of the controller relay when connecting 10 A 3 Inductive load and follow the instructions of the manufacturer of the pump which...

Страница 6: ...s turned on if the measured temperature is higher than the set temperature The switching sensitivity is taken into account when switching F2 Control of a cooling system s circulating pump the output i...

Страница 7: ...ches the connected pump on off below above the set temperature The lower this value is the more constant the temperature of the circulating fluid will be The switching sensitivity can be set between 0...

Страница 8: ...the function is on the output will turn on every 5 days for 15 seconds if the output has not been turned on in the last 5 days During this time will appear on the display instead of the measured temp...

Страница 9: ...e measured temperature reach es 5 C again to protect the pump and the heating system During this time the display alternates between and the measured temperature When the frost protection function is...

Страница 10: ...itching sensitivity of 1 0 C the pump connected to it switches ON and at temperatures below 39 0 C the output switches OFF the pump connected to it switches OFF In F2 mode the output switches exactly...

Страница 11: ...t accuracy 1 0 C Power supply 230 V AC 50 Hz Output voltage 230 V AC 50 Hz Loadability max 10 A 3 Inductive load Environmental protection IP40 Immersion sleeve connector size G 1 2 8x60 mm Length of h...

Страница 12: ...he requirements of standards EMC 2014 30 EU LVD 2014 35 EU and RoHS 2011 65 EU Manufacturer QUANTRAX Kft H 6726 Szeged F lem le u 34 Telefon 36 62 424 133 Fax 36 62 424 672 E mail iroda quantrax hu We...

Отзывы: